Overview of alarms 06/2009
SINAMICS alarms
2-290
© Siemens AG 2009 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2009
%2Bus number/station number
Causes of error:
Bus peripheral has no voltage
Bus address set incorrectly
Bus connection faulty
Active MD 11240 (SDB configuration) is set incorrectly
Reaction: PLC Stop
Remedy: Rectify the error using the error cause
Program Con-
tinuation:
Switch control OFF - ON.
2.6 SINAMICS alarms
A detailed description of the SINAMICS alarms is provided in the following
publication:
LH1, SINAMICS_S Parameter Manual, Chapter: Faults and Warning
Structure of the SINAMICS alarms
Each alarm (fault or warning) consists of a number, local ID (optional) and alarm
text.
Number range
Numbers range from 200 000 to 299 999.
Notation
In the SINAMICS_S List Manual, faults and warnings start with letter "F" and a
following five-digit number.
Example:
You can find a description of alarm number 207016 in the SINAMICS_S List Man-
ual under No. F07016.