NCK alarms
06/2009 Overview of alarms
2-27
© Siemens AG 2009 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2009
Take greater care when optimizing the clock times MD10050 $MN_SYSCLOCK_CYCLE_TIME,
MD10060 $MN_POSCTRL_SYSCLOCK_TIME_RATIO and/or MD10070
$MN_IPO_SYSCLOCK_TIME_RATIO.
The test should be performed with an NC program that represents the highest possible control load.
To be on the safe side, a margin of 15 to 25% should be added to the times determined in this way.
Program Con-
tinuation:
Switch control OFF - ON.
4260 Machine data %1 illegal
Parameters: %1 = String: MD identifier
Definitions: The selected cam pair was not activated by MD10450 $MN_SW_CAM_ASSIGN_TAB, or several cam
pairs were selected.
Reaction: Mode group not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Activate the cam pair or select only one cam pair.
Program Con-
tinuation:
Switch control OFF - ON.
4270 Machine data %1 assigns not activated NCK input/output byte %2
Parameters: %1 = String: MD identifier
%2 = Index
Definitions: The specified machine data assigns a digital input/output byte or an analog input/output signal the pro-
cessing of which has not been activated to an NC function.
Reaction: NC not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Please inform the authorized personnel/service department.
Correct machine data. Activate required inputs/outputs via MDs:
MD10350 $MN_FASTIO_DIG_NUM_INPUTS
MD10360 $MN_FASTIO_DIG_NUM_OUTPUTS
MD10300 $MN_FASTIO_ANA_NUM_INPUTS
MD10310 $MN_FASTIO_ANA_NUM_OUTPUTS
Activation of fast inputs/outputs does not require the corresponding hardware configuration to be
available at the control. All functions using fast inputs/outputs can also be made use of by the PLC
specification/modification defined in the VDI interface, if the response time requirements are reduced
accordingly.
Activated inputs/outputs increase the computation time requirement of the interpolation cycle because
the PLC manipulation signals are handled cyclically. Note: Deactivate any inputs/outputs not in use.
Program Con-
tinuation:
Switch control OFF - ON.
4275 Machine data %1 and %2 both assign the same NCK output byte no. %3
several times
Parameters: %1 = String: MD identifier
%2 = String: MD identifier
%3 = No. of output
Definitions: The specified machine data assign two NC functions to the same digital/analog output.
Reaction: NC not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Please inform the authorized personnel/service department. Correct machine data.