PROFIBUS alarms
06/2009 Overview of alarms
2-281
© Siemens AG 2009 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2009
2.4 PROFIBUS alarms
380001 PROFIBUS/PROFINET: Startup error, reason %1 parameter %2 %3 %4.
Parameters: %1 = Cause of the error
%2 = Parameter 1
%3 = Parameter 2
%4 = Parameter 3
Definitions: An error occurred during startup of the PROFIBUS/PROFINET master.
Overview: Cause of the error, Par 1, Par 2, Par 3:
- 01 = DPM version, DPM version, DPA version, --
- 02 = DPM ramp-up timeout, DPM actual value status, DPM setpoint value status, --
- 03 = DPM ramp-up status, DPM actual value status, DPM setpoint value status, DPM error code
- 04 = DPM ramp-up error, DPM actual value status, DPM setpoint value status, DPM error code
- 05 = DPM-PLL sync error, --, --, --
- 07 = Alarm queue too long, Actual number, Setpoint number, --
- 08 = Unknown client, Client ID, --, --
- 09 = Client version, Client ID, Client version, DPA version
- 10 = Too many clients, Client number, max. number of clients, --
- 11 = Log.basic address used several times; bus no.; slot no.; log.basic address --
- 20 = Slave/device address used several times, slave/device address --
- 21 = Slave/device address unknown, slave/device address, --
- 22 = Erroneous configuration telegram, slave/device address, error code, --
- 23 = OMI incompatible (data), drive version, CDA version, --, --
- 24 = OMI incompatible (driver), drive version, CDA version, --, --
- 25 = CPI initialization failed, error code, --, --, --
- 26 = DMA not active
- 27 = Reserved
- 28 = Reserved
- 29 = Reserved
- The 1000s digit of the error cause = number of the affected bus
Clients are the following components of the control system that use the PROFIBUS/PROFINET:
Client ID = 1: PLC
Client ID = 2: NCK
Possible causes are:
- Error in contents of SDB
- Corruption of parts of the system program
- Hardware defect on NC component
Reaction: Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy: Remedy for 1-11
1. Check the control project, check MD11240 $MN_PROFIBUS_SDB_NUMBER, and reload it when
using a user-specific SDB.
2. If the error still occurs, back up data, and restart the control with the standard values as per the as-
delivered condition.
3. In case of correct ramp-up, reload the user data stage by stage.
4. If the error still occurs during ramp-up with standard values, reboot the system from the PC card or
update the software.
5. If the error still occurs, replace the hardware.
Remedy for 20-21
1. Check/correct the addresses of the connected slaves/devices.
Remedy for 22
See SINAMICS warning 1903 for a description of the meaning behind the error codes.
1. Control the SDB
- Check the type and length of the message frame
- Match slot assignment with P978
2. Evaluate the drive alarms/warnings
Remedy for 23-24
1. Software replacement required
Remedy for 25