Page 80 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Testing the Configuration
The effect of the ARROW key is determined by the state (rate of rise or fall) immediately
before the key is pressed.
When the level rises to 100% or falls to 0%, it reverses direction at the same rate.
Checking Volume Characterization
To confirm universal volume calculations (P050 = 9, 10) are correct:
1. Go to P920
2. Key in a level associated with a known volume
3. Press ENTER
4. Check the returned volume against the manufacturer’s chart
5. Change parameters P054 and P055, as required
6. Repeat steps 2 to 5 until the volume curve is verified
Checking OCM Flow Characterization
To confirm universal flow calculations (P600 = 4, 5) are accurate:
1. Go to P925
2. Enter a level with a known flow
3. Press ENTER
4. Check the returned flow against the manufacturer’s chart
5. Change parameters P610 and P611, as required
6. Repeat steps 2 to 5 until the flow curve is verified
Action State (prior to pressing key) Effect
Press
Stop Rise at 1% of Span / second
Rise at 1% of Span / second Rise at 4% of Span / second (max.)
Rise at 4% of Span / second (max.) No effect
Fall at 1% of Span / second Stop
Fall at 4% of Span / second Fall at 1% of Span / second
Press
Stop Fall at 1% of Span / second
Rise at 1% of Span / second Stop
Rise at 4% of Span / second (max.) Rise at 1% of Span / second
Fall at 1% of Span / second Fall at 4% of Span / second (max.)
Fall at 4% of Span / second (max.) No effect