Page 200 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
Advanced Shot Adjustment (P840 to P852)
These parameters are for Siemens Milltronics service personnel only.
P840 Short Shot Number
The number of short shots to be fired (and results averaged) per transmit pulse.
P841 Long Shot Number
Enter the number of long shots to be fired (and results averaged) per transmit pulse.
This value is automatically altered by Maximum Process Speed (P003).
P842 Short Shot Frequency
Adjust the short shot transmit pulse frequency (in kHz).
This feature is automatically altered when Transducer (P004) is altered.
Primary Index Global
Values
Range: 0 to 100
Preset: 1
Related
• P841 Long Shot Number
• P842 Short Shot
Frequency
• P844 Short Shot Width
• P850 Short Shot Bias
• P851 Short Shot Floor
• P852 Short Shot Range
Primary Index Global
Values
Range: 0 to 200
Preset: 5
Altered By • P003 Maximum Process Speed
Related
• P840 Short Shot Number
• P843 Long Shot Frequency
• P845 Long Shot Width
Primary Index Global
Values Range: 42kHz to 46kHz
Altered By •P004 Transducer
Related
• P840 Short Shot Number
• P844 Short Shot Width
• P850 Short Shot Bias
• P851 Short Shot Floor
• P852 Short Shot Range