7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 175
mmmmm
Parameters
P702 Filling Indicator
The fill rate required to activate the LCD Filling indicator ( ).
This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of
the Max Fill Rate (P700).
P703 Emptying Indicator
The empty rate required to activate the LCD Emptying indicator ( ).
This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of
the Max Empty Rate (P701).
P704 Rate Filter
Damps Rate Value (P707) fluctuations.
Primary Index Global
Values Range: -999 to 9999
Altered by P003 Maximum Process Speed
Related
P005 Units
P007 Span
P700 Max Fill Rate
Primary Index Global
Values Range: -999 to 9999
Altered by P003 Maximum Process Speed
Related
P005 Units
P007 Span
P701 Max Empty Rate
Primary Index Global
Values
0 Rate display not required
Filtered Output
1 Continuously filtered and updated
Interval Output
2 1 minute or 50 mm (2 in)
3 5 minutes or 100 mm (3.9 in)
4 10 minutes or 300 mm (11.8 in)
5 10 minutes or 1000 mm (39.4 in)