7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 121
mmmmm
Parameters
Entering a Volume Breakpoint
1. Go to Parameter P055.
2. For each index enter a volume.
3. Ensure that each volume corresponds to the same index for P054.
For more on
Volume Characterization
, go to page 44.
Display and Reading (P060 to P062)
These parameters are used to:
• Change the number of decimal places displayed
• Convert the Reading to alternate units
• Reference measurements to other than Empty (P006) or Span (P007)
P060 Decimal Position
Defines the maximum number of decimal places used on the LCD.
In RUN mode, the decimal position adjusts to prevent the number of digits from exceeding
the display capabilities. To keep the decimal place from shifting, reduce the number of
decimal places to that shown at 100%.
Example:
If 100% is 15m, use two decimal places for sample readings of 15.00 or 12.15.
P061 Convert Reading
Multiplies the current value by the specified amount to allow for scaling.
Primary Index Level
Values
0 No digits after the decimal point
1 1 digit after the decimal point
2 * 2 digits after the decimal point
3 3 digits after the decimal point (limited by device resolution)
Alters • P607 Flowrate Decimal
Altered by
•P005 Units
• P051 Maximum volume
Related • P920 Reading Measurement
Primary Index Level
Values
Range: -999 to 9999
Preset: 1.000
Related • P920 Reading Measurement