Page 6 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Specifications
Discrete (2)
10-50Vdc switching level
logical 0 = < 0.5 Vdc
logical 1 = 10 to 50 Vdc
3mA maximum draw
Enclosure
240mm (9.5") x 1.75mm (6.9"). Width dimension includes hinges.
Type 4X / NEMA 4X / IP 65
1
Polycarbonate
Weight
1.37 kg (3.02 lb)
Approvals
See product nameplate
Compatible Transducers
Echomax series and STH series
Transducers
Base
single point (44 kHz)
second transducer can only be used for average or differential
Cable
Do not use coaxial cable for transducers (see General Appendix F: Upgrading on
page 234 for more information).
2-3 copper conductors, twisted with shield, drain wire, 300Vrms, 0.5mm
2
(22-18AWG),
nominal capacitance between adjacent conductors @ 1kHz = 19 pF/ft., nominal
capacitance between conductor and shield @ 1kHz = 33 pF/ft. (Belden 8760 is
acceptable)
365m (1200 ft) maximum
1.
For watertight applications, use only approved, suitable size hubs in the
enclosure’s conduit holes.
Note: The HydroRanger 200 is to be used only in the manner outlined in this
instruction manual or protection provided by the equipment may be impaired.