Page 58 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Pump Control
Totalizing Pumped Volume
Prerequisite: the volume of the vessel must be known.
Set in RUN Mode
1. Press PROGRAM for RUN mode.
2. Press TOGGLE to display pumped volume on the totalizer.
3. Press AUXILIARY to display current level in the auxiliary reading area.
Setting Independent Failsafe Controls
Independent failsafe controls allow you to vary an individual relay from the global failsafe
controls programmed in P070 to P072.
Example:
The global failsafe controls are set to hold and Relay Five is set to trigger an alarm bell.
Parameter Index Value Description
P001 G 7 Operation = pumped volume
P002 G 1
These parameters are as shown above.
P003 G 2
P004 G 102
P005 G 1
P006 G 1.8
P007 G 1.4
P050 G 1 Tank shape is Flat Bottom.
P051 G 17.6
Max volume is 17.6m
3
or 17,600 liters.
P111 1 52
Sets relays 1, 2, and 3 as a pump group using
ALTERNATE DUTY ASSIST CONTROL.
P111 2 52
P111 3 52
P112 1 1.0
Sets the ON setpoints for the pump group.
P112 2 1.2
P112 3 1.4
P113 0 0.2 Sets the OFF setpoints for the pump group.
Parameter Index Value Description
P071 G HOLd Keep level at last known value.
P129 5 dE De-energize Relay Five, and trigger alarm.