Page 156 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P337 Auto Record LOE Time
Limits Auto Profile Records from being saved unless extended LOE occurs.
If the LOE condition exceeds the period entered, the Echo Profile is saved. When set for 0
LOE is not required for an Auto Profile Record to be saved.
Installation Records (P340 to P342)
P340 Date of Manufacture
View the date of manufacture of this HydroRanger 200 unit.
P341 RUN Time
View the number of days this HydroRanger 200 has been in operation.
The RUN Time value is updated once a day, and cannot be reset. However, in the event of
a power interruption, the counter won’t advance. Therefore, a unit that is powered down
on a regular basis will not have an accurate value.
Primary Index Global
Values
Range: 0.0 to 9999 (seconds)
Preset: 0.0
Related
P334 Auto Record ON Setpoint
P335 Auto Record OFF Setpoint
P336 Auto Record Filling / Emptying
Primary Index Global
Values Format: YY:MM:DD (view only)
Related
P340 Date of Manufacture
P342 Start Ups
Primary Index Global
Values Range: 0.000 to 9999 (view only)
Related
P340 Date of Manufacture
P342 Start Ups