Page 186 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P782 Parameter Index Location
Determines where index information is stored for the parameter access area.
Global (0)
The primary and secondary index values are global (they affect all of the parameter
access area at once) and stored in:
primary index – R43,999
secondary index – R43,998
Parameter-Specific (1)
The primary and secondary index values are encoded into the format words found
between R46,000 and R46,999. Each format work corresponds with the R44,000 series
number in the parameter access map. For example, the format register R46,111
corresponds to the parameter P111 and the value is stored in R44,111. If the Modbus
protocol (P770 = 2 or 3) is not used this parameter is ignored.
SmartLinx Hardware Testing
These parameters are used to test and debug a SmartLinx card.
P790 Hardware Error
The results of ongoing hardware tests in the communications circuitry.
If a test does not meet PASS requirements, communication halts and tests repeated until
PASS requirements are met. Communication then resumes.
Primary Index Global
Values
0 * Global
1 Parameter-Specific
Altered By P770 Port Protocol
Primary Index Global
Values
PASS * No e rrors
FAIL Faulty SmartLinx module or HydroRanger 200
ERR1 Unknown protocol, upgrade software
Related
P791 Bus Error
P792 Bus Error Count