Parameters
mA Output Failsafe (P219)
P219 mA Output Failsafe
Use for failsafe operation, independent of the Failsafe Material Level (P071).
Selecting an independent mA Failsafe option:
1. Press MODE to display the Auxiliary Function symbol.
2. Press ARROWS to scroll access the failsafe options.
3. Press ENTER when the desired option displayed.
Or, to produce an mA output at a specific value, enter the value required. This is used only
if mA output is allocated to a transducer (P201 = 1 to 7).
mA Input (P250 to P260)
P250 mA Input Range
Shows the mA input range of the connected mA device.
Ensure this range corresponds to the output range of the external device. All level
measurements will equate % of Span with the % of the mA range.
Primary Index mA output
Values
Range: 0.000 to 22.00
OFF * mA output responds to Failsafe Material Level (P071).
HOLd
last known value is held until normal operation
resumes
LO produce the Empty mA output immediately
HI produce the Span mA output immediately
Related • P201 mA Output Function
Primary Index Global
Values
1 0 to 20 mA
2*4 to 20 mA