Página 1 - HYDRORANGER 200

HYDRORANGER 200Instruction Manual October 2002HYDRORANGER 200

Página 2 - Disclaimer of Liability

viiimmmmmTable of ContentsP622 Inflow / Discharge Adjust...

Página 3

Page 86 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmCommunications InstallationCommunications InstallationWiring Guidelines• the RJ-11 cable

Página 4

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 87mmmmmCommunications InstallationPort 1: RS-232 RJ-11 Jack To connect the unit to a PC using a

Página 5

Page 88 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmCommunications InstallationTo connect the unit to a modem using an RS-485 port:Configuri

Página 6

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 89mmmmmCommunications InstallationP772 Baud RateThe communication rate with the master device.T

Página 7

Page 90 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmCommunications InstallationP778 Modem AvailableSets the HydroRanger 200 to use an extern

Página 8

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 91mmmmmModbus Register TypesModbus Register MapFeatures affecting volume, mA input, and Average

Página 9

Page 92 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmModbus Register TypesThe HydroRanger 200 was designed to make it easy for master devices

Página 10 - Table of Contents

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 93mmmmmModbus Register TypesProduct ID (R40,064)Identifying Milltronics device type:Point Data

Página 11

Page 94 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmModbus Register TypesDiscrete Inputs (R41,070) This table shows the current status of th

Página 12

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 95mmmmmModbus Register TypesPump OFF Setpoint (R41,430 – R41,435) The OFF setpoint level (P113)

Página 13

ixmmmmmTable of ContentsP773 Parity ...

Página 14

Page 96 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmModbus Register TypesUsually, the parameters are all read / write.Each parameter registe

Página 15

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 97mmmmmModbus Register TypesGlobal Index Method (P782 = 0)Global format method sets index value

Página 16 - Configuration Examples

Page 98 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmModbus Register Types2. Read the value from the appropriate parameter register (the exam

Página 17 - Specifications

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 99mmmmmModbus Register TypesGlobal Index Method (P782 = 0)Only the final digit of the format wo

Página 18

Page 100 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmModbus Register TypesExamples of using the format word for both the index values and th

Página 19

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 101mmmmmData TypesData TypesThe HydroRanger 200 parameters do not always use integers to hold v

Página 20 - Transducers

Page 102 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmData TypesFor example, if R41,442 is read as a UINT32, the 32 bits would look like this

Página 21 - Installation

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 103mmmmmData TypesText MessagesIf a Milltronics device parameter returns a text message, that m

Página 22 - Mounting Instructions

Page 104 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmData TypesRelay Function Codes (P111 Only) If a Milltronics device parameter returns a

Página 23 - HydroRanger 200 Board

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 105mmmmmError HandlingError HandlingModbus ResponsesWhen polled by a Modbus Master, a slave dev

Página 24 - Optional Equipment

xmmmmmTable of ContentsP901 Memory ...

Página 25 - Please note:

Page 106 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmError Handling• If P000 is activated, then the value will be ignored and no error respo

Página 26 - Terminal Board

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 107mmmmmError HandlingCommunication TroubleshootingGenerally1. Check the following:• There is p

Página 27

Page 108 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmCommunication Appendix ACommunication Appendix A: Single Parameter Access (SPA)This App

Página 28 - Temperature Sensor

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 109mmmmmCommunication Appendix AWriting ParametersTo set parameters through Modbus do the follo

Página 29 - Level System Synchronization

Page 110 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmCommunication Appendix AError CodesThe error codes returned in the format area are 8-bi

Página 30 - Digital Communications

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 111mmmmmParametersParameter ReferenceThe HydroRanger 200 is configured through its parameters,

Página 31 - Operating the HydroRanger 200

Page 112 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersNotes

Página 32 - Readings in RUN Mode

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 113mmmmmParametersP000 LockSecures the HydroRanger 200 from changes. Access this parameter dire

Página 33 - Controlling the Display

Page 114 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersFor these operations any of three level points (transducer 1, transducer 2, o

Página 34 - Auxiliary Reading

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 115mmmmmParametersP004 TransducerSpecifies the Siemens Milltronics transducer connected to the

Página 35 - PROGRAM Mode

ximmmmmTable of ContentsObstructions in the Sound Beam ... 223

Página 36 - Starting PROGRAM Mode

Page 116 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP006 EmptyEnter distance in units (P005) from the face of the transducer to t

Página 37 - Programmer Keys

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 117mmmmmParametersAlways prevent the monitored surface from approaching within 0.33m (1 ft) of

Página 38 - Dolphin Plus

Page 118 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersValues4 Half Sphere Bottom5 Flat Sloped Bottom6Flat Ends7 Parabola Ends8 Sphe

Página 39 - Dolphin Plus Toolbar Buttons

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 119mmmmmParametersP051 Maximum Volume For Readings in volumetric units (rather than percent), e

Página 40 - Security

Page 120 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP054 Level Breakpoints (Universal Volume Calculation)When the tank shape is t

Página 41 - Parameters Types

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 121mmmmmParametersEntering a Volume Breakpoint1. Go to Parameter P055.2. For each index enter a

Página 42 - Display Readout

Page 122 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersExamples: • If the measured value is in feet, enter 0.3333 to display the num

Página 43

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 123mmmmmParametersP065 Reading Override ValueThis value is substituted for the current reading

Página 44 - Accessing a Parameter Index

Page 124 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersFailsafe (P070 to P072) P070 Failsafe TimerThe time for invalid measurements

Página 45 - Primary and Secondary Indexes

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 125mmmmmParametersSelecting HI, LO, or HOLd1. Press FUNCTION to display the Auxiliary Functio

Página 47 - Measurement Conditions

Page 126 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersRelays (P100 to P119)The HydroRanger 200 has six relays (or digital outputs)

Página 48 - Relay Function

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 127mmmmmParametersP110 Level SourceSets the level source on which the indexed relay is assigned

Página 49 - 2 % of span

Page 128 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP112 Relay ON SetpointSets the process point at which the relay changes from

Página 50 - Relay Related Parameters

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 129mmmmmParametersP113 Relay OFF SetpointSets the process point at which the relay returns to i

Página 51 - Relay Activation

Page 130 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP118 Relay Output LogicThe logic applied to relays to determine the contact o

Página 52 - Preset Applications

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 131mmmmmParametersP119 Relay Logic TestForces the relay control logic into an ACTIVATED or DE-A

Página 53 - Value # Parameters Affected

Page 132 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP122 Pump Service Ratio Selects pump usage based on the RUN time ratio rather

Página 54

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 133mmmmmParametersTo select an independent Relay Failsafe value:1. Press FUNCTION to display

Página 55 - Discrete Inputs

Page 134 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP131 Pump Run-On Duration Sets the number of seconds that the pump runs on.Yo

Página 56 - Level Reading Parameters

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 135mmmmmParametersP133 Pump Power Resumption Delay Sets the minimum delay before the first pump

Página 57 - Verifying the mA Range

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 1mmmmmHydroRanger 200HydroRanger 200The HydroRanger 200 is a single-point, six relay device tha

Página 58 - Tank Shape and Dimensions

Page 136 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP137 Pump Group Puts pumps into groups for multiple pump rotations on one tra

Página 59 - Characterization Chart

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 137mmmmmParametersP170 Flush Pump Picks the number of the pump relay which triggers the flushin

Página 60

Page 138 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP173 Flush Duration The length of time for each flush cycle that the flush co

Página 61 - Set the Common Parameters

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 139mmmmmParametersP201 mA Output Function Alters the mA output/measurement relationship.P202 mA

Página 62 - Setting Simple Level Alarms

Page 140 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP203 mA Output Value / Transducer Displays current mA output value for the Po

Página 63 - Temperature

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 141mmmmmParametersP210 0/4 mA Output Setpoint Sets the process level corresponding to the 0 or

Página 64 - Loss of Echo (LOE)

Page 142 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP213 mA Output Max Limit Sets the maximum mA output value (in mA) to be produ

Página 65 - Pump Control

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 143mmmmmParametersmA Output Failsafe (P219) P219 mA Output Failsafe Use for failsafe operation,

Página 66 - HydroRanger

Page 144 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP251 0 or 4 mA Input Level Shows the process level corresponding to the 0 or

Página 67

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 145mmmmmParametersP254 Scaled mA Input Value Shows the resulting level value after scaling.This

Página 68 - Other Pump Control Algorithms

Page 2 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmHydroRanger 200Manual SymbolsPlease note their use carefully.Configuration ExamplesThe co

Página 69

Page 146 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP275 Scaled Discrete Input ValueShows the current value of the discrete input

Página 70 - Optional Pump Controls

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 147mmmmmParametersP300 Temperature, Transducer MaximumShows the highest temperature encountered

Página 71 - Single Point Mode

Page 148 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP303 Temperature, Sensor MinimumShows the lowest temperature encountered, as

Página 72 - Totalizing Pumped Volume

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 149mmmmmParametersPump Records (P310 to P312)These features to identify pump usage and if the a

Página 73 - Reducing Wall Cling

Page 150 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP312 Pump Run Ons View or reset the accumulated number of times the displayed

Página 74 - Setting a Flush Valve

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 151mmmmmParametersLCD Totalizer (P322 and P323) Use these features to view, reset, or preset th

Página 75 - Tracking Pump Usage

Page 152 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersProfile Records (P330 to P337) These features can record up to ten Echo profi

Página 76 - Rake (Screen) Control

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 153mmmmmParametersRecording a profile manuallyPress TRANSDUCER to fire the transducer and rec

Página 77 - Set Relay 1 (Operate Rake)

Page 154 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP332 Auto Record TransducerSpecifies the Transducer Point Number for which Au

Página 78 - Totalizer

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 155mmmmmParametersP334 Auto Record ON SetpointEnter the critical level which, in conjunction wi

Página 79 - Flow Sampler

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 3mmmmmSpecificationsSpecificationsPowerAC version• 100-230 Vac ± 15%, 50 / 60 Hz, 36 VA (17W)1•

Página 80 - Common Parameters

Page 156 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP337 Auto Record LOE TimeLimits Auto Profile Records from being saved unless

Página 81 - Setting Zero Head

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 157mmmmmParametersP342 Start UpsThe number of times power has been applied since the Date Of Ma

Página 82 - Setting Totalized Volume

Page 158 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersIf your PMD is not listed, select the appropriate Universal Flow Calculation.

Página 83 - Parameter Index Value

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 159mmmmmParametersExample ExponentsP602 Primary Measuring Device Dimensions The dimensions of t

Página 84 - Palmer Bowlus Flume

Page 160 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP603 Maximum Head The level value associated with Maximum Flow, in Units (P00

Página 85

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 161mmmmmParametersP605 Zero Head The distance above Empty (P006) in Units (P005) representing z

Página 86 - Applicable Weir Profiles

Page 162 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP607 Flowrate Decimal The maximum number of decimal places to be displayed.In

Página 87 - Parshall Flume

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 163mmmmmParametersThis parameter is enabled only if the primary measuring device (PMD) supports

Página 88 - Leopold Lagco Flume

Page 164 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP620 Low Flow Cutoff Eliminates totalizer activity for flows at or below the

Página 89 - Cut Throat Flume

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 165mmmmmParametersPumped Volume Totalizer (P622) The Pumped Volume Totalizer is a HydroRanger 2

Página 90 - Universal Calculation Support

Page 4 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmSpecificationsRange• 0.3m (1 ft) to 15m (50 ft), dependent on transducerAccuracy• 0.25% o

Página 91 - Example Weirs

Page 166 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersTotalizer (P630 to P645) P630 LCD Totalized Multiplier Use this feature if th

Página 92

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 167mmmmmParametersP633 LCD Totalized Decimal Position Enter the maximum number of decimal place

Página 93 - Testing the Configuration

Page 168 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP641 Flow Sampler Mantissa Use this feature in conjunction with Flow Sampler

Página 94

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 169mmmmmParametersP645 Relay Duration Use this feature (if desired) to adjust the minimum conta

Página 95 - Application Test

Page 170 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersBefore using this feature, verify the following parameters are correct:•Empty

Página 96

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 171mmmmmParametersP652 Offset CorrectionThe value altered when an Offset Calibration is perform

Página 97 - Optional SmartLinx

Page 172 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersTemperature Compensation (P660 to P664)P660 Temp SourceSource of the temperat

Página 98 - Communication Ports

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 173mmmmmParametersP663 Temperature Transducer AllocationThis feature may only be used for diffe

Página 99 - SmartLinx

Page 174 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersRate (P700 to P708) These parameters determine how material level changes are

Página 100 - Communications Installation

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 175mmmmmParametersP702 Filling IndicatorThe fill rate required to activate the LCD Filling indi

Página 101 - Port 2: RS-485

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 5mmmmmSpecificationsFixed• 0.17% per °C deviation from programmed valueOutputsTransducer drive•

Página 102 - P771 Network Address

Page 176 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersEnter the time or distance interval over which the Rate Value is to be calcul

Página 103 - P773 Parity

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 177mmmmmParametersP708 Volume Rate Display The rate of change of volume in percent of maximum v

Página 104 - P782 Parameter Index Location

Page 178 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersIf a material agitator (mixer) is used in the vessel monitored, set Echo Lock

Página 105 - Modbus Register Map

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 179mmmmmParametersP713 Echo Lock WindowAdjusts the size of the Echo Lock Window.The Echo Lock W

Página 106 - Map ID (R40,063)

Page 180 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersThis feature may only be used to adjust the delay before the next point is sc

Página 107 - Product ID (R40,064)

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 181mmmmmParametersSelecting the Auxiliary Reading operation1. Press READING to display the Au

Página 108 - Relay Data Address

Page 182 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP733 Scroll AccessUse this feature to select the parameter scroll access opti

Página 109

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 183mmmmmParametersSmartLinx Reserved (750 to 769) These parameters are reserved for optional Sm

Página 110 - Reading Parameters

Page 184 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP772 Baud RateThe communication rate with the master device.This specifies th

Página 111 - Types of values are:

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 185mmmmmParametersP775 Stop BitsThe number of bits between the data bits.P778 Modem AvailableSe

Página 112 - Writing Parameters

© Siemens Milltronics Process Instruments Inc. 2002Safety GuidelinesWarning notices must be observed to ensure personal safety as well as that of oth

Página 113 - Format Registers

Page 6 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmSpecificationsDiscrete (2)• 10-50Vdc switching level• logical 0 = < 0.5 Vdc• logical 1

Página 114

Page 186 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP782 Parameter Index LocationDetermines where index information is stored for

Página 115 - Data Types

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 187mmmmmParametersP791 Bus ErrorIndicates if an error condition is occurring on the bus.P792 Bu

Página 116 - Split Values

Page 188 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP801 Range ExtensionAllows the material level to fall below the Empty setting

Página 117 - Text Messages

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 189mmmmmParametersP803 Shot / Pulse ModeDetermines what type of ultrasonic shots are fired.Use

Página 118 - HydroRanger 200

Page 190 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP805 Echo ConfidenceDisplays the echo confidence of the measurement echo from

Página 119 - Error Handling

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 191mmmmmParametersAdvanced Echo Processing (P810 to P825) The following parameters are for auth

Página 120

Page 192 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersAny combination of the following Scope Displays is available. Two methods to

Página 121 - Communication Troubleshooting

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 193mmmmmParametersP816 Echo Time RawThe time (in ms) from the transmit pulse to the processed e

Página 122 - Parameter Access (SPA)

Page 194 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP818 Profile Pointer DistanceThe distance between the transducer face and the

Página 123 - Format Register

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 195mmmmmParametersUse this to select the algorithm(s) the Sonic Intelligence®echo selection is

Página 124 - Error Codes

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 7mmmmmInstallationInstallationMountingMounting LocationsRecommended• Ambient temperature is alw

Página 125 - Parameter Reference

Page 196 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP823 Reform Echo Smoothes jagged peaks in the echo profile.Use this feature,

Página 126 - Parameters

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 197mmmmmParametersAdvanced TVT Adjustment (P830 to P835) The following parameters are for autho

Página 127 - Quick Start (P001 to P007)

Page 198 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP832 TVT Shaper AdjustAllows manual adjustment of the TVT curve.Use this feat

Página 128 - P003 Maximum Process Speed

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 199mmmmmParametersP833 TVT Start MinUse this feature to adjust the TVT Curve height to ignore f

Página 129 - P005 Units

Page 200 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersAdvanced Shot Adjustment (P840 to P852) These parameters are for Siemens Mill

Página 130 - P007 Span

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 201mmmmmParametersP843 Long Shot FrequencyAdjust the long shot transmit pulse frequency (in kHz

Página 131 - Volume (P050 to P055)

Page 202 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP850 Short Shot BiasUse this feature to slant the echo evaluation in favour o

Página 132

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 203mmmmmParametersTest (P900 to P913)Test Parameters are intended for use by Siemens Milltronic

Página 133 - P053 Tank Dimension L

Page 204 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP904 KeypadPress ENTER , then press each keypad key in the following sequen

Página 134 - Typical volume calculations

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 205mmmmmParametersP910 Toggle RelaysUsed to energize and de-energize relays directly.Enter the

Página 135 - P061 Convert Reading

Page 8 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmInstallationMounting InstructionsMount the unit where there is sufficient room to swing l

Página 136 - Backup Level Override

Page 206 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP913 Sensor TemperatureAccess this parameter to display the temperature in °C

Página 137 - P066 Override Time Delay

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 207mmmmmParametersReading Measurements by OperationP921 Material MeasurementThe distance in Uni

Página 138 - Failsafe (P070 to P072)

Page 208 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP924 Volume Measurement The calculated vessel capacity in Max Volume (P051) o

Página 139 - P072 Failsafe Level Advance

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 209mmmmmParametersMaster Reset (P999) This feature resets all parameters to original values.Use

Página 140 - Relays (P100 to P119)

Page 210 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersNotes

Página 141 - P111 Relay Control Function

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 211mmmmmAppendix A: Index TypesGeneral Appendix A: Index typesIndex typesName Description # of

Página 142 - P112 Relay ON Setpoint

Page 212 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix B: Tech ReferenceGeneral Appendix B: Technical ReferenceTransmit PulseThe tran

Página 143 - P116 Dead Band

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 213mmmmmAppendix B: Tech ReferenceDolphin Plus DisplayDistance CalculationTo calculate the tran

Página 144 - P118 Relay Output Logic

Page 214 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix B: Tech ReferenceThe HydroRanger 200 automatic temperature compensation is bas

Página 145 - P121 Pump by Rate

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 215mmmmmAppendix B: Tech ReferenceEnter a Level Breakpoint at each point where the level/volume

Página 146 - P129 Relay Failsafe

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 9mmmmmInstallationCable routed through a conduit:1. Remove the four mounting screws holding the

Página 147 - P130 Pump Run-On Interval

Page 216 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix B: Tech ReferenceEnter a Head Breakpoint at each point where the head/flow cur

Página 148 - P132 Pump Start Delay

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 217mmmmmAppendix B: Tech ReferenceMaximum Process SpeedThe HydroRanger 200’s ability to respond

Página 149 - P136 Wall Cling Reduction

Page 218 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix C: TroubleshootingGeneral Appendix C: TroubleshootingIf the setup becomes too

Página 150 - Flush Systems (P170 to P173)

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 219mmmmmAppendix C: TroubleshootingNoise ProblemsIncorrect readings can be the result of noise

Página 151 - P172 Flush Interval

Page 220 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix C: TroubleshootingDetermine the Noise SourceDisconnect the transducer from the

Página 152 - P200 mA Output Range

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 221mmmmmAppendix C: TroubleshootingFiltering cables is an option but is not recommended unless

Página 153 - P202 mA Output Allocation

Page 222 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix C: TroubleshootingMeasurement DifficultiesIf the Failsafe Timer (P070) expires

Página 154 - Settings

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 223mmmmmAppendix C: TroubleshootingDisplaying Echo Confidence in the RUN modePress and hold f

Página 155 - P212 mA Output Min Limit

Page 224 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix C: TroubleshootingIf an obstruction cannot be removed or avoided, adjust the T

Página 156 - P215 20 mA Output Trim

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 225mmmmmAppendix C: TroubleshootingWrong ReadingIf the Reading is erratic, or jumps to some inc

Página 157 - P250 mA Input Range

Page 10 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmInstallationInstalling the BatteryThe battery (Rayovac BR2032) has a ten-year life expec

Página 158 - P252 20 mA Input Level

Page 226 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix C: TroubleshootingNormal Ring DownPoor Ring DownRing down times that extend pa

Página 159 - P270 Discrete Input Function

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 227mmmmmAppendix D: Pump Control General Appendix D: Pump Control ReferenceThe HydroRanger 200

Página 160

Page 228 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix D: Pump Control AlternateStarts pumps based on the duty schedule and always le

Página 161

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 229mmmmmAppendix D: Pump Control Relay TableThe following table shows relay status when each se

Página 162 - P305 Reading Min

Page 230 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix D: Pump Control Alternate Duty Backup (P111 = 53) Alternates the lead pump eac

Página 163 - Pump Records (P310 to P312)

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 231mmmmmAppendix D: Pump Control Service Ratio Duty Assist (P111 = 54) Selects the lead pump ba

Página 164 - Flow Records (P320 and P321)

Page 232 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix D: Pump Control First In First Out (FIFO) (P111 = 56) Selects the lead pump ba

Página 165 - P323 LCD Total High

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 233Appendix E: Updfate SoftwareGeneral Appendix E: Updating SoftwareUpdating SoftwareTo update

Página 166 - P330 Profile Record

Page 234 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmGeneral Appendix FGeneral Appendix F: UpgradingThe following procedure will assist you

Página 167 - P331 Auto Record Enable

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 235mmmmmGeneral Appendix FConnecting a transducer with RG62 coaxial extension cableIf you are r

Página 168 - P333 Auto Record Interval

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 11mmmmmWiringWiringPlease note:• Verify that all system components are installed in accordance

Página 169 - P335 Auto Record OFF Setpoint

Page 236 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmGeneral Appendix FHydroRanger to HydroRanger 200 ParametersThe HydroRanger 200 uses the

Página 170 - P341 RUN Time

7ML1998IFC01 HydroRanger 200 – INSTRUCTION MANUAL Page 237mmmmmIndexIndexAaccuracy 4adding new functions 233alarm 47bounded 49cable fault 49common pa

Página 171 - P342 Start Ups

Page 238 HydroRanger 200 – INSTRUCTION MANUAL 7ML1998IFC01mmmmmIndexcut throat 75H flume 71Leopold Lagco 74Palmer Bowlus 70Parshall 73, 77rectangular

Página 172 - P601 Flow Exponent

7ML1998IFC01 HydroRanger 200 – INSTRUCTION MANUAL Page 239mmmmmIndexoverview 95reading 96writing 98parameter indexing 29, 96parametersadvanced echo p

Página 173 - Example Exponents

Page 240 HydroRanger 200 – INSTRUCTION MANUAL 7ML1998IFC01mmmmmIndexrecording profiles 153register map 91discrete inputs 94input/output 93mA output 94

Página 174 - P604 Maximum Flow

7ML1998IFC01 HydroRanger 200 – INSTRUCTION MANUAL Page 241mmmmmIndexcalculation 214characterization chart 45dimensions 33readings 44tank shape 44univ

Página 175 - P606 Time Units

*7ML19981Fc01*Rev. 1.2

Página 176 - P608 Flowrate Units

Page 12 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmWiringTerminal BoardThe terminal board on the HydroRanger 200 allows all inputs and outp

Página 177 - P611 Breakpoint Flowrates

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 13mmmmmWiringTransducersA 0.1 µF (100V or greater) capacitor is included with the HydroRanger 2

Página 178 - P621 Auto Zero Head

Page 14 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmWiringTemperature SensorAccurate temperature readings are critical to accurate level mea

Página 179

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 15mmmmmWiringLevel System SynchronizationWhen using multiple ultrasonic level monitors, be sure

Página 180 - Totalizer (P630 to P645)

immmmmTable of ContentsTable of ContentsHydroRanger 200 ...

Página 181 - Example:

Page 16 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmWiringDigital CommunicationsWiring the HydroRanger 200 for communications allows it to b

Página 182 - P642 Flow Sampler Exponent

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 17mmmmmOperationOperating the HydroRanger 200The HydroRanger has two modes of operation: RUN an

Página 183 - P650 Offset Calibration

Page 18 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationIcons indicating index type (Item 1) edited in PROGRAM mode:Readings in RUN Mod

Página 184

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 19mmmmmOperationStatus ParametersStatus parameters give the operating status of the HydroRanger

Página 185 - P654 Velocity at 20°C

Page 20 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationExampleTo reference the displayed level to sea level, enter the distance in Uni

Página 186 - P661 Temp Fixed

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 21mmmmmOperationSetting a Specific Auxiliary ReadingTo display a second auxiliary reading, pres

Página 187 - P664 Temperature

Page 22 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationStarting PROGRAM ModeHand ProgrammerThe hand programmer gives you direct access

Página 188 - Rate (P700 to P708)

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 23mmmmmOperationProgrammer KeysKeys Programming Mode Run Mode1 8-digit Totalizer (toggle) 2 Pum

Página 189 - P704 Rate Filter

Page 24 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationDolphin PlusUse Dolphin Plus software to configure, monitor, tune, and diagnose

Página 190 - P707 Rate Value

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 25mmmmmOperationDolphin Plus Toolbar ButtonsThe toolbar buttons provide quick access to Dolphin

Página 191 - P711 Echo Lock

iimmmmmTable of ContentsUsing Units or Percent (%) ...

Página 192 - P712 Echo Lock Sampling

Page 26 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationActivating the HydroRanger 200All the instructions in the following procedures

Página 193 - P727 Scan Delay

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 27mmmmmOperationWhen P000 is set to 1954, programming is enabled. To disable programming, enter

Página 194 - Display (P730 to P739)

Page 28 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationParameter ResetReturning a parameter to factory default.1. Display the appropri

Página 195 - P732 Display Delay

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 29mmmmmOperationChanging Parameters (Dolphin Plus)The other method for changing parameter value

Página 196 - P737 Primary Reading

Page 30 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationHydroRanger 200 DisplayThe index number and the index values are displayed abov

Página 197

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 31mmmmmOperationPrimary and Secondary IndexesPrimary Index: relates to direct input or output a

Página 198

Page 32 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationExample P054 provides up to 32 breakpoint levels used with P055 (Volume Breakpo

Página 199

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 33mmmmmOperationMeasurement ConditionsThe following information will help you configure your Hy

Página 200 - SmartLinx Hardware Testing

Page 34 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmRelays3RelaysRelays are the primary controls of external devices such as pumps or alarms

Página 201 - P800 Near Blanking

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 35mmmmmRelaysTemperature In high alarm, the function goes on when the temperature rises to the

Página 202 - P801 Range Extension

iiimmmmmTable of ContentsOther Pump Control Algorithms ...

Página 203 - P804 Confidence Threshold

Page 36 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmRelaysRelay Status – Non Run Modes When the fail-safe timer expires, pump control relays

Página 204 - P807 Noise

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 37mmmmmRelaysP111–Control FunctionsThe control function energizes the relay coils. When the ins

Página 205 - P810 Scope Displays

Page 38 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmRelaysFunctions affected by setpoint are configured by parameters that determine the app

Página 206 - P815 Echo Time Filtered

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 39mmmmmRelaysReservoir 13Pump up with the following level settings:ParameterRelay #123456P111 5

Página 207 - P817 Profile Pointer Time

Page 40 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmBackup Level OverrideBackup Level OverrideBackup level override provides the option of o

Página 208 - P820 Algorithm

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 41mmmmmDiscrete InputsDiscrete InputsWiring the Discrete InputsNormal state is standard operati

Página 209 - P822 Narrow Echo Filter

Page 42 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmmA I/OmA I/OTo integrate the HydroRanger 200 with other equipment, use the mA input and

Página 210 - P825 Echo Marker Trigger

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 43mmmmmmA I/OCalibrating 4 mA Output1. Connect the mA receiving device to the HydroRanger 200.

Página 211 - P831 TVT Shaper

Page 44 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmVolumeVolume Volume is used in two situations:1. Calculate and display volume instead of

Página 212 - P832 TVT Shaper Adjust

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 45mmmmmVolumeCharacterization Chart If you cannot use a pre-defined tank, then use one of the u

Página 213 - P835 TVT Slope Min

ivmmmmmTable of ContentsSimulating a Level Cycle ...

Página 214 - P842 Short Shot Frequency

Page 46 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmVolumeParameter Transducer Index Value DescriptionP054 110.0Determines the Level breakp

Página 215 - P845 Long Shot Width

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 47mmmmmAlarmsAlarmsLevelThe level alarm is the most common. Use this alarm to warn you when you

Página 216 - P852 Short Shot Range

Page 48 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAlarmsSetting Simple Level AlarmsTo set Relay Five to a standard level alarm (Hi Hi, Hi,

Página 217 - Test (P900 to P913)

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 49mmmmmAlarmsIn Bounds / Out of Bounds Range Use the bounded range alarms to detect when the le

Página 218 - P908 Scanner

Page 50 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAlarmsWith P112 and P113, you can set a high alarm (P112 > P113) or a low alarm (P112

Página 219 - P912 Transducer Temperature

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 51mmmmmPump ControlPump ControlSetting a Pump Down GroupExample: Sewage Wet WellSetting a group

Página 220 - Measurement (P920 to P927)

Page 52 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmPump ControlSet Relays to ALTERNATE DUTY ASSIST Set the ON SetpointsSet the OFF Setpoint

Página 221 - P923 Distance Measurement

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 53mmmmmPump ControlSet the Common Parameters Prerequisite: Substitute the details of your appli

Página 222 - P927 Distance Measurement

Page 54 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmPump ControlOther Pump Control AlgorithmsSet Relays to ALTERNATE DUTY BACKUP Set the Rel

Página 223 - Master Reset (P999)

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 55mmmmmPump ControlSet Relays to FIXED DUTY BACKUP Set the Relay ON Setpoints Set the Relay OFF

Página 224

vmmmmmTable of ContentsBit Values ...

Página 225 - Index types

Page 56 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmPump ControlSet Relays to FIRST IN FIRST OUT (FIFO) ASSIST Set the Relay ON Setpoints Se

Página 226 - Echo Processing

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 57mmmmmPump ControlWhen the first ON setpoint is reached, the pumps will start, one by one, unt

Página 227 - Sound Velocity

Page 58 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmPump ControlTotalizing Pumped Volume Prerequisite: the volume of the vessel must be know

Página 228 - Volume Calculation

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 59mmmmmPump ControlSetting a Pump to Run On When you need to pump below the normal OFF setpoint

Página 229 - Flow Calculation

Page 60 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmPump ControlExample :A range of 0.5 meters is used to vary the setpoint. The randomly-se

Página 230 - Universal, Curved

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 61mmmmmPump ControlExample: The flush valve connects to Relay Four and the watched pump is on R

Página 231 - Maximum Process Speed

Page 62 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01Rake (Screen) Control Rake (Screen) Control Screens or rakes are mounted on the inflow channe

Página 232 - Common Problems Chart

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 63mmmmmRake (Screen) ControlSetting the Common ParametersPrerequisite: Substitute the details o

Página 233 - Noise Problems

Page 64 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmExternal Totalizers and Flow Samplers External Totalizers and Flow Samplers External tot

Página 234 - Non-Transducer Noise Sources

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 65mmmmmExternal Totalizers and Flow Samplers The source of units depends on the operation:Flow

Página 235 - Reducing Acoustical Noise

vimmmmmTable of ContentsRelays (P100 to P119) ...

Página 236 - Measurement Difficulties

Page 66 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringOpen Channel Monitoring (OCM) An OCM installation is defined one

Página 237 - Fixed Reading

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 67mmmmmOpen Channel MonitoringSetting Zero HeadMany PMDs start flowing higher than the traditio

Página 238 - Nozzle Mountings

Page 68 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringSetting Totalized VolumeTo display the totalized volume on the LC

Página 239 - Transducer Ringing

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 69mmmmmOpen Channel MonitoringBS-3680 / ISO 4359 Rectangular FlumeParameter Index ValueP600 G 6

Página 240 - Poor Ring Down

Page 70 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringPalmer Bowlus FlumeApplication Information• Sized by pipe diamete

Página 241 - Reference

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 71mmmmmOpen Channel MonitoringH Flume• Sized by maximum depth of flume• Approach is preferably

Página 242 - Off 0 Off Off Off

Page 72 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringPMDs with Exponential Flow to Head FunctionFor Primary Measuring

Página 243

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 73mmmmmOpen Channel MonitoringNon-Applicable Weir ProfilesFlows through these weirs can be meas

Página 244

Page 74 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringLeopold Lagco FlumeApplication Information• Designed to be instal

Página 245 - P122 Index Value

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 75mmmmmOpen Channel MonitoringCut Throat FlumeApplication Information• Similar to Parshall flum

Página 246 - Other Pump Controls

viimmmmmTable of ContentsP270 Discrete Input Function...

Página 247 - Updating Software

Page 76 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringUniversal Calculation SupportWhen the primary measuring device (P

Página 248 - General Appendix F: Upgrading

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 77mmmmmOpen Channel MonitoringExample FlumesThese example flumes would both require a universal

Página 249 - Existing installation

Page 78 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringNotes

Página 250 - Relay Parameter Value

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 79mmmmmTesting the ConfigurationTesting the ConfigurationAfter programming the unit, you must t

Página 251

Page 80 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmTesting the ConfigurationThe effect of the ARROW key is determined by the state (rate of

Página 252

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 81mmmmmTesting the ConfigurationI/O CheckoutAfter you have installed the unit, we recommend tha

Página 253

Page 82 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmTesting the ConfigurationMonitor system performance carefully, under all anticipated ope

Página 254

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 83mmmmmCommunicationsHydroRanger 200 CommunicationsHydroRanger 200 Communication SystemsThe Hyd

Página 255

Page 84 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmCommunicationsCommunication SystemsThe HydroRanger 200 is capable of communicating with

Página 256 - *7ML19981Fc01*

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 85mmmmmCommunicationsSmartLinxOther protocols are available through optional SmartLinx communic