Page 190 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P805 Echo Confidence
Displays the echo confidence of the measurement echo from the last shot.
Use this feature to monitor the effect of transducer aiming, location, and mechanical
transducer / mounting isolation.
Both short and long shot Echo Confidence is displayed. (To display this value in the
auxiliary display while the unit is running, press for 4 seconds.)
P806 Echo Strength
Displays the strength (in dB above 1 uV RMS) of the selected measurement echo.
P807 Noise
Displays the average and peak ambient noise (in dB above 1 uV RMS) being processed.
The noise level is a combination of transient acoustic noise and electrical noise (induced
into the transducer cable or receiving circuitry). See
Noise Problems
in the
Troubleshooting Section
on page 219.
Primary Index Transducer
Values
Format: x:y (view only)
x = short (0 to 99)
y = long (0 to 99)
Related P804 Confidence Threshold P830 TVT Type
Display Description
x:--
short shot confidence value, (long shot not used).
--:y
long shot confidence value, (short shot not used).
x:y short and long shot confidence values (both used).
E transducer cable is open or short circuited.
--:-- no shots were processed for Sonic Intelligence® evaluation.
Primary Index Transducer
Values Format: 0 to 99 (view only)
Primary Index Transducer
Values
Format: x:y (view only)
x = average (-99 to 99)
y = peak (-99 to 99)
Vista de página 203