7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 115
mmmmm
Parameters
P004 Transducer
Specifies the Siemens Milltronics transducer connected to the unit.
P005 Units
Specifies measurement units used for dimensional values.
Changing this value automatically changes the units displayed for many parameters.
Existing values are converted and do not have to be re-entered.
Global
Values
0 * No transducer attached (preset for Dual Point)
1ST-25
2ST-50
100 STH
101 XCT-8
102 * XPS-10 (preset for Standard Mode)
103 XCT-12
104 XPS-15
112 XRS-5
250 mA input
Related
• mA Input (P250 to P260)
• P842 Short Shot Frequency
• P843 Long Shot Frequency
• P844 Short Shot Width
• P845 Long Shot Width
• P852 Short Shot Range
Primary Index Global
Values
1*Meters
2 Centimeters
3 Millimeters
4Feet
5 Inches
Alters
•P006 Empty
•P007 Span
• P060 Decimal Position
• P603 Maximum Head
• P605 Zero Head
• P620 Low Flow Cutoff
• P921 Material Measurement
• P926 Head Measurement
• P927 Distance Measurement