Operation
Icons indicating index type (Item 1) edited in PROGRAM mode:
Readings in RUN Mode
Change the displayed values with the keys on the hand programmer. All readings are
shown in the Auxiliary field, except for the totalizer and P920.
Icon Index Type
measurement point or transducer
relay
secondary index
mA input or output
Key Function P#
Toggle Readings between percent and units:
• Level: 0 – 100%
• Space or Distance:
1
100% – 0
1.
Distances less than 0.3m (12") from the transducer face cannot be measured
reliably. Therefore, a 0% reading is not possible during Distance operation.
P920
+
Accumulated pump running hours
2
for numbered pump.
2.
If the associated relay is programmed for pump control.
P310
+
Hold number key for five seconds to display the number of
accumulated pump starts
2
for numbered pump.
P311
Eight-digit totalizer, uses index and reading areas, press
again to toggle, P737 sets default.
Used for OCM and Pumped Volume.
P322
P323
P920
Head measurement P926
Instantaneous flow based on head (OCM) P925
mA Output value P203
Tem pe rat ur e P664
Rate of level change P707
Failsafe Time Left (in %). When the Reading is updated,
this value (Auxiliary Reading) resets to 100 and begins to
decrease until the next valid measurement is made. If the
Failsafe Time Left reaches 0, LOE flashes in the display.
Hold for four seconds to show echo confidence P805
+ ###
Display the value of the entered parameter which is global
or indexed by transducer
Auxiliary reading displays parameter specified in P731 P731
Distance P923
P
P