Page 208 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P924 Volume Measurement
The calculated vessel capacity in Max Volume (P051) or % of Max Volume.
P925 Flow Measurement
The calculated flowrate in Max Flow (P604) units or % of Max Flow.
P926 Head Measurement
Corresponds to Head (the distance from Zero Head (P605) to the monitored surface) in
Units (P005) or % of Span (P007).
P927 Distance Measurement
The distance between the surface and the transducer face.
Use P923 unless the distance information is required in percent.
Primary Index Global
Values Range: 0.000 to 9999
Related • P051 Maximum Volume
Primary Index Global
Values Range: 0.000 to 9999
Related • P604 Maximum Flow
Primary Index Global
Values Range: -999 to 9999
Related
•P005 Units
•P007 Span
• P605 Zero Head
Primary Index Transducer
Values Range: 0.000 to 9999
Related
• P005 Units
• P006 Empty