7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 119
mmmmm
Parameters
P051 Maximum Volume
For Readings in volumetric units (rather than percent), enter the vessel volume between
Empty (P006) and Span (P007).
Any volume units can be chosen because volume is calculated from empty to maximum
span and is scaled according to the Tank Shape (P050) value.
P052 Tank Dimension A
Dimension A as used in P050 Tank Shape.
Enter one of the following:
• height of the tank bottom if P050 = 2,3,4, or 5
OR
• length of one end section of the tank if P050 = 7, in Units (P005)
P053 Tank Dimension L
Dimension L as used in P050 Tank Shape.
Enter the following:
• tank length (excluding both end sections) if P050 = 7
Primary Index Global
Values
Range: 0.000 to 9999
Preset: 100.0
Alters P060 Decimal Position
Related
•P006 Empty
•P007 Span
• P924 Volume Measurement
Primary Index Global
Values
Range: 0.0 to 9999
Preset: 0.000
Related • P050 Tank Shape
Primary Index Global
Values
Range: 0.0 to 9999
Preset: 0.000
Related • P050 Tank Shape
Note: Make sure selected chosen
units allow LCD volume display.
Examples:
• If max. volume = 3650 m
3
, enter 3650
• If max. volume = 267500 gallons, enter
267.5 (thousands of gallons)