Overview of alarms 06/2007
NCK alarms/ISO alarms
2-32
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007Edition
4282 Hardware of external NCK outputs assigned repeatedly
Definitions: Several outputs have been configured on the same hardware byte.
Reaction: NC not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Please inform the authorized personnel/service department. Alter MD 10364
HW_ASSIGN_DIG_FASTOUT or MD 10364 HW_ASSIGN_ANA_FASTOUT.
Program Con-
tinuation:
Switch control OFF - ON.
4285 Error on terminal block %1, error code %2
Parameters: %1 = Number of terminal block (1 ... 4)
%2 = Error code
Definitions: An error occurred on terminal block no. %1 (sign-of-life failure, I/O module removed in current opera-
tion, etc.). All possible errors which can lead to this alarm are not yet known (and will be completed
later). Further information together with a description of the error code and its meaning will be provided
at a later date.
Error code 1: Sign-of-life failure from terminal block
Error code 10: Sign-of-life failure NC
Reaction: NC not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Please inform the authorized personnel/service department. Check hardware.
Program Con-
tinuation:
Switch control OFF - ON.
4290 Sign of life monitoring: local P-bus not alive
Definitions: The COM computer must alter the sign-of-life on the local P-bus in each SERVO cycle. Monitoring for
alteration takes place in the IPO cycle. If the sign of life has not altered, this alarm is triggered.
Reaction: NC not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Please inform the authorized personnel/service department. Check hardware.
Program Con-
tinuation:
Switch control OFF - ON.
4291 Failure of module in local P-bus slot %1, error codes %2 %3 %4
Parameters: %1 = Slot number
%2 = Error code
%3 = Error code
%4 = Error code
Definitions: The module on the specified slot has signaled a diagnostics alarm. The error code reported corre-
sponds to the AS300 documentation.
Reaction: NC not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Please inform the authorized personnel/service department. Check hardware.