Overview of alarms 06/2007
NCK alarms/ISO alarms
2-16
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007Edition
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
2900 Reboot is delayed
Definitions: This alarm indicates a delayed reboot.
The alarm occurs only when the reboot is carried out by the HMI and the MD 10088
REBOOT_DELAY_TIME is set higher than zero.
The alarm can be suppressed with SUPPRESS_ALARM_MASK BIT 20.
Reaction: NC not ready.
The NC switches to follow-up mode.
Mode group not ready, also effective for single axes
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Alarm reaction delay is cancelled.
Remedy: See MD 10088 REBOOT_DELAY_TIME and
MD 11410 SUPPRESS_ALARM_MASK
Program Con-
tinuation:
Switch control OFF - ON.
3000 Emergency stop
Definitions: The EMERGENCY STOP request is present at the NC/PLC interface
(V 26000000.1).
Reaction: NC not ready.
Mode group not ready, also effective for single axes
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Alarm reaction delay is cancelled.
Remedy: Check that an EMERGENCY STOP cam was not approached and that no EMERGENCY STOP but-
ton was pressed. Check PLC user program.
Corrected the cause of EMERGENCY STOP and acknowledge it via the NC/PLC interface (V
26000000.2).
Program Con-
tinuation:
Teileprogramm neu starten.Clear alarm with the RESET key in all channels of this mode group.
Restart part program.
3001 Internal emergency stop
Definitions: This alarm is not displayed.
Reaction: NC not ready.
Local alarm reaction.
Mode group not ready, also effective for single axes
NC Start disable in this channel.
NC Stop on alarm.
Remedy: No remedy required
Program Con-
tinuation:
Teileprogramm neu starten.Clear alarm with the RESET key in all channels of this mode group.
Restart part program.
4000 Channel %1 machine data %2[%3] has gap in axis assignment
Parameters: %1 = channel number
%2 = string: MD identifier
Definitions: The assignment of a machine axis to a channel by the machine data 20070
AXCONF_MACHAX_USED must be contiguous. At system power-up (Power On) gaps are detected
and displayed as an alarm.
Reaction: NC not ready.
Mode group not ready, also effective for single axes
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.