6.5.12 Measured value display
Note
To
use the operating functions with the buttons, first set the device variable (DV) parameters
with a host system such as SIMATIC PDM. You will finds details of the relation between
primary variable (PV) assignment and the DV in the following section:
Measuring mode "Pressure" (Page 101)
Introduction
In mode 13, adjust the following types of measured value display:
● mA
● %
● Display of the PV selected via HART. (Default setting: P pressure)
Table 6-6 Display of measuring mode/device variables
Display DV Meaning
P 0 Pressure
t-SE 1 Sensor temperature
t-EL 2 Electronics temperature
P-UNC 3 Pressure (untrimmed)
LEVEL 4 Level
Vol 5 Volume
MASS 6 Mass
V-Flo 7 Volumetric flow rate (not relevant for gauge or absolute pressure)
M-Flo 8 Mass flow rate (not relevant for gauge or absolute pressure)
CUSt 9 Users
Condition
You are familiar with the correct operation of the transmitter and the associated safety notes.
Procedure
To select the display type, proceed as follows:
1.
Set mode 13.
2. Select the measured value display.
3. Save with the [M] button.
Operation
6.5 Local operation
SITRANS P, DS III series with HART
94 Operating Instructions, 09/2012, A5E00047092-08