Hysteresis Operating point for chatter suppression in the case of small pressure
changes.
Response time The time which must pass after the limit is violated before this violation
is registered.
Stop time The time for which a limit interrupt or warning will always be sustained
even when the event which triggered it is no longer present.

>V@
)DXOW
FXUUHQW
0LQVWRSWLPH
7LPH
5HVSRQVHWLPH

,>P$@
'9PD[
'9PLQ
'9
Figure 7-19 Trip levels for the limit monitor
You can count the limit violations for each limit monitor by activating an event counter that
provides
separate, cumulative totals of upper and lower limit violations. A diagnostic warning
and / or a diagnostic interrupt can be issued once a certain number of violations is reached, a
number which you can also program. You can program the following values for the event
counter:
Table 7-6 Parameters of the event counter
Event counter: upper limit Select here whether a warning or a warning plus an interrupt should be
triggered when the comparison value is exceeded.
Event counter: lower limit Select here whether a warning or a warning plus an interrupt should be
triggered when the comparison value is not met.
Comparison value: upper limit Specify here the number of overflows at which a warning or a warning
plus an interrupt should be triggered.
Comparison value: upper limit Specify here the number of underflows at which a warning or a warning
plus an interrupt should be triggered.
Limit monitoring, warning/interrupt: upper limit Select whether a warning or a warning plus an interrupt should be
triggered when the event counter upper limit is violated.
Limit monitoring, warning/interrupt: lower limit Select whether a warning or a warning plus an interrupt should be
triggered when the event counter lower limit is violated.
Operating functions through HART
7.23 Limit monitor
SITRANS P, DS III series with HART
Operating Instructions, 09/2012, A5E00047092-08 135