6.4.2 Units display
Description
The unit display comprises five 14-segment fields for representing the unit as a percentage
value, physical unit or current value. A bar graph showing the percentage measured value
range
from 0 to 100% can be displayed as an alternative to the unit. The bar graph function is
disabled by default.
Display
Figure 6-2 Examples for measured value display for current and bar graph
The following messages may appear as a ticker in the bottom line of the display. They have
no influence on the current output.
Table 6-2
Message as ticker
Ticker Meaning
"DIAGNOSTIC WARNING" Is always displayed if:
● An event configured by the user is to be signaled with a
warning. For example:
– Limit reached
– Event counter for limit values exceeded
– Calibration time expired
– Current saturation reached
● The status of one of the device variables is "UNCERTAIN".
"SIMULATION" Is always displayed when the simulation of a pressure value or
temperature value is active.
See also
Measured value status
(Page 110)
Operation
6.4 Display
SITRANS P, DS III series with HART
68 Operating Instructions, 09/2012, A5E00047092-08