6.4.2 Units display
Description
The unit display comprises five 14-segment fields for representing the unit as a percentage
value, physical unit or current value. A bar graph showing the percentage measured value
range
from 0 to 100% can be displayed as an alternative to the unit. The bar graph function is
disabled by default.
Display
Figure 6-2 Examples for measured value display for current and bar graph
The following messages may appear as a ticker in the bottom line of the display. They have
no influence on the current output.
Table 6-2
Message as ticker
Ticker Meaning
"DIAGNOSTIC WARNING" Is always displayed if:
An event configured by the user is to be signaled with a
warning. For example:
Limit reached
Event counter for limit values exceeded
Calibration time expired
Current saturation reached
The status of one of the device variables is "UNCERTAIN".
"SIMULATION" Is always displayed when the simulation of a pressure value or
temperature value is active.
See also
Measured value status
(Page 110)
Operation
6.4 Display
SITRANS P, DS III series with HART
68 Operating Instructions, 09/2012, A5E00047092-08