① Turning range
② Retaining screw
③ Orientation mark
Figure 4-4 Example: turning range of transmitters for pressure and absolute pressure from the gauge
pressure series
The turning range for transmitters for differential pressure and flow rate, absolute pressure
from the differential pressure series and level is identified in a similar manner.
Procedure
NOTICE
Follow the turning range, otherwise electrical connections of the measuring cell may get
damaged.
1. Loosen the retaining screw ② (Allen screw 2.5 mm).
2.
Turn the electronic housing against the measuring cell. Follow the marked turning range
① while doing so.
3. Tighten the retaining screw (torque: 3.4 to 3.6 Nm).
4.7 Rotating the display
You can rotate the display in the electronics enclosure. This makes it easier to read the display
if the device is not being operated in a vertical position.
Procedure
1. Unscrew the cover of the electrical cable compartment. See section Structure (Page 19).
An identification text "FIELD TERMINAL" is provided at the side of the housing.
2. Unscrew the display. Depending on the application position of the transmitter, you can
reinstall it at four different positions. You can turn it by ±90° or ±180°.
Installing/mounting
4.7 Rotating the display
SITRANS P, DS III series with HART
Operating Instructions, 09/2012, A5E00047092-08 55