Condition
You are familiar with the correct operation of the transmitter and the associated safety notes.
You have not created any reference pressure and have selected a pressure unit.
Procedure
To the set the start of scale value blindly, proceed as follows:
1.
Set mode 5.
2. Press the [↑] and [↓] buttons simultaneously for 2 seconds.
6.5.5.3 Blind setting of full scale value
Introduction
Blind setting resets the full scale value to the upper sensor limit.
Note
Changes
in modes 5 and 6 have an exclusive effect on pressure scaling. This does not affect
the scaling for level or customized characteristic curve. Therefore, only measured pressure
values and pressure units are displayed in these modes.
Condition
You are familiar with the correct operation of the transmitter and the associated safety notes.
You have not created any reference pressure and have selected a pressure unit.
Procedure
To the set the full scale value blindly, proceed as follows:
1.
Set mode 6.
2. Press the [↑] and [↓] buttons simultaneously for 2 seconds.
Operation
6.5 Local operation
SITRANS P, DS III series with HART
Operating Instructions, 09/2012, A5E00047092-08 85