WARNING
Improper connection after maintenance
Danger of explosion in areas subject to explosion hazard.
●
Connect the device correctly after maintenance.
● Close the device after maintenance work.
Refer to Chapter "Connecting (Page 57)".
WARNING
Use of a computer in a hazardous area
If
the interface to the computer is used in the hazardous area, there is a danger of explosion.
● Ensure that the atmosphere is explosion-free (hot work permit).
CAUTION
Releasing key lock
Improper modification of parameters could influence process safety.
● Make
sure that only authorized personnel may cancel the key locking of devices for safety-
related applications.
CAUTION
Hot surfaces
Danger
of burns during maintenance work on parts having surface temperatures exceeding
70 °C (158 °F).
● Take corresponding protective measures, for example by wearing protective gloves.
● After carrying out maintenance, remount touch protection measures.
CAUTION
Hazardous voltage with open device in versions with 4-conductor extension
Danger of electrocution when the enclosure is opened or enclosure parts are removed.
●
Disconnect the device before you open the enclosure or remove enclosure parts.
● Observe the special precautionary measures if maintenance is required while the device
is live. Have maintenance work carried out by qualified personnel.
Service and maintenance
10.1 Basic safety instructions
SITRANS P, DS III series with HART
Operating Instructions, 09/2012, A5E00047092-08 161