1. Create the reference pressure.
2.
Set mode 7.
3. Set the reference pressure on the display.
4. Save using the [M] key.
6.5.7 Current transmitter
Introduction
In mode 8, switch the pressure transmitter into the constant current operation. You can connect
an external current transmitter in the constant current operation. The current then no longer
corresponds to the process variable. The following output current can be adjusted irrespective
of the input pressure:
● 3.6 mA
● 4.0 mA
● 12.0 mA
● 20.0 mA
● 22.8 mA
You can use HART communication to adjust intermediate values.
Procedure
To switch on the constant current operation, proceed as follows:
1. Set mode 8.
"Cur" in the display stands for current.
2. Press the [↑] and [↓] buttons simultaneously.
3. Select constant current.
Switching off the constant current operation
To switch off the constant current operation, proceed as follows:
Press the [M] button in mode 8.
Operation
6.5 Local operation
SITRANS P, DS III series with HART
88 Operating Instructions, 09/2012, A5E00047092-08