6.5.3.2 Setting/adjusting the start of scale value
NOTICE
Inadvertent adjustment of parameters on devices without display or without visible display
Key lock is canceled if you press the [M] key for longer than 5 seconds, see chapter
"Releasing key lock or function lock
(Page 91)". In the case of a device without display or
without a visible display, you could inadvertently change parameters.
● Always press the [M] key for less than 5 seconds.
Introduction
Set or adjust the start of scale value of the pressure transmitter in mode 2.
You
can also adjust the start of scale value or the full scale value separately as well as adjust
both these values one after the other.
Condition
You are familiar with the correct operation of the transmitter and the associated safety notes.
You have selected a reference pressure that corresponds to the start of scale value and is
within the permissible tolerance range.
The transmitter is in "Pressure" measuring mode.
Setting start of scale value
To set the output current of the start of scale value to 4 mA, proceed as follows:
1. Create the reference pressure.
2. Set mode 2.
3. Set the start of scale value to 4 mA.
4. Save with the [M] button.
Adjusting start of scale value
If you do not set the output current but constantly adjust it, you need to calculate the currents
to be adjusted mathematically.
To the adjust the output current of the start of scale value, proceed as follows:
1. Create the reference pressure.
2. Set mode 2.
3. Adjust the output current of the start of scale value to the calculated value.
4. Save with the [M] button.
Operation
6.5 Local operation
SITRANS P, DS III series with HART
Operating Instructions, 09/2012, A5E00047092-08 79