C 14 bar process pressure is created.
Use the [M] button to set the transmitter to mode 3. To set the full scale value, press the
[↑] and [↓] buttons simultaneously for 2 seconds.
If there is 14 bar input pressure, the transmitter produces an output current of 20 mA.
D The output current can be calculated for any input pressure using the "current calculation
formula for setting".
Note
If
the value exceeds or falls below the preset measuring limits by more than 20% when setting,
the setting function is not carried out. The old value is retained in this case.
With a marked elevation of the zero point, the full scale value must therefore previously be
reduced such that it still lies within the permitted range after elevation of the zero point. This
setting function is only possible in "Pressure" measuring mode.
Adjusting with reference pressure
Condition:
The reference pressure, the adjusted start of scale value and adjusted full scale value are
known.
When
adjusting, a start of scale value or a full scale value can be allocated to a desired current
value with the aid of a reference pressure. This function is particularly suitable when the
required pressures for the start of scale value and the full scale value are not available After
adjustment, the measuring range specified on the nameplate may no longer correspond to the
setting made.
Using the formulae below, the current to be set for the desired start of scale value and the full
scale value can be calculated.
To calculate the output currents when setting the start of scale value or the full scale value,
the reference pressure must be selected such that a value between 4 and 20 mA results for
the current.
,
S0
$
0(0$
P$P$
,
0(
S
UH
I
0$
WDUJHW
0(
WDUJHW
0$
WDUJHW
P$P$
I Output current MA
actual
Old start of scale value
I
MA
Current to be adjusted with MA
target
ME
actual
Old full scale value
I
ME
Current to be adjusted with ME
target
MA
target
New start of scale value
p Pressure ME
target
New full scale value
p
ref
Existing reference pressure
Figure 6-7 Current calculation formula for setting with reference pressure
Operation
6.5 Local operation
SITRANS P, DS III series with HART
Operating Instructions, 09/2012, A5E00047092-08 77