6.4.3 Error display
Description
If hardware faults, software errors or diagnostic alarms occur in the transmitter, the message
"Error" appears in the measured value display.
A ticker appears in the bottom line of the display indicating the type of error. This diagnostic
information is also available via HART communication.
Display
Figure 6-3 Example of error message
The following messages may appear as a ticker in the bottom line of the display.
Ticker Meaning
"HARDWARE FIRMWARE ALARM" Contains hardware faults such as:
incorrect checksum
incorrect EEPROM data
Defective EEROM
RAM fault
ROM fault
inconsistent data
EEPROMs not initialized
"DIAGNOSTIC ALARM" Is always displayed if
an
event configured by the user is to be signaled with
an alarm.
For example:
Limit reached
Event counter for limit values exceeded
Calibration time expired
Current saturation reached
the status of one of the device variables is "BAD".
"SENSOR BREAK" Appears when there is a sensor break.
See also
Measured value status
(Page 110)