Condition
You are familiar with the correct operation of the transmitter and the associated safety notes.
You have not created any reference pressure and have selected a pressure unit.
Procedure
To the adjust the pressure value of the full scale value blindly, proceed as follows:
1.
Set mode 6.
2. Adjust the pressure value of the full scale value.
3. Save with the [M] button.
6.5.6 Trimming the zero point
Introduction
The zero point is calibrated in mode 7. Zero point calibration corrects zero point errors resulting
from the installation position of the pressure transmitter. The device type determines the way
in which you proceed.
SIMATIC PDM or the HART communicator will display the total of all zero point corrections.
Condition
You are familiar with the correct operation of the transmitter and the associated safety notes.
Zero point calibration for gauge pressure transmitter
To calibrate the zero point, proceed as follows:
1. Pressurize the transmitter.
2. Set mode 7.
3. Press the [↑] and [↓] keys simultaneously for 2 seconds.
4. Save using the [M] key.
Zero point calibration for absolute pressure transmitter
Note
You need a reference pressure known to you which lies within the measuring limits.
To calibrate the zero point, proceed as follows:
Operation
6.5 Local operation
SITRANS P, DS III series with HART
Operating Instructions, 09/2012, A5E00047092-08 87