In case of defect, you can replace the electronic unit by following the warning notes and the
provided instruction manual.
See also
Error display
(Page 69)
10.2.4 Changing the measuring cell and application electronics
Related
Each of the individual components "Measuring cell" and "Electronics" has a non-volatile
memory (EEPROM).
Measuring cell data (e.g.: measuring range, measuring cell material, oil filling) and application-
specific electronics data (e.g.: downscaling, additional electrical damping) are located in the
measuring cell EEPROM. Application-specific data are lost when the measuring cell is
changed. Application-specific data are not lost when the application electronics are changed.
You can backup application-specific data before changing the measuring cell and reload them
afterwards. Use an input device which supports the HART protocol. (e.g. HART communicator,
PC with HART modem and HART software or PC with HART modem and PDM software).
Factory settings will be used if application-specific data are not backed up before the measuring
cell is changed.
Technical developments enable advanced functions to be implemented in the firmware of the
measuring cell or application electronics. Further technical developments are indicated by
modified firmware statuses (FW). The firmware status does not affect whether the modules
can be replaced. However, the scope of functions is limited to the function of existing
components.
If a combination of certain firmware versions of measuring cell and application electronics is
not possible for technical reasons, the device will identify this problem and go into "Fault
current" mode. This information is provided via the HART interface.
10.3 Cleaning
WARNING
Dust layers above 5 mm
Danger of explosion in hazardous areas. Device may overheat du to dust build up.
Remove any dust layers in excess of 5 mm.
Service and maintenance
10.3 Cleaning
SITRANS P, DS III series with HART
164 Operating Instructions, 09/2012, A5E00047092-08