Configuring with Web Based Management
5.10 "iFeatures" menu
SCALANCE W770/W730 to IEEE 802.11n Web Based Management
264 Configuration Manual, 11/2014, C79000-G8976-C323-03
Access point mode
You are using an access point in access point mode.
Description
The table has the following columns:
Radio
Specifies the WLAN interface to which the settings relate.
Enable iPCF
Enable or disable iPCF mode. For PNIO communication, we recommend that you enable
the iPCF mode. By enabling iPCF, the data rates provided by the access point are
adapted. We strongly recommend that you retain the default setting for the data rates
(802.11 a/b/g = 12 Mbps and 802.11n = MCS 2).
PNIO Support
Enable or disable optimized support of PNIO.
iPCF Cycle Time [ms]
Select the required cycle time from the drop-down list.
The following points need to be taken into account when setting the cycle time. Otherwise
it may not be possible to establish stable communication.
There is only one access point in the system; in other words, the clients move only in
one wireless cell. In this case, update times >= 16 ms are supported.
There are several access points in the system that communicate over different
channels. The clients roam between the access points. In this case, select update
times >= 32 ms.
In addition to the guide values shown above, remember that the shortest cycle time to be
set is calculated according to the formula "2 ms * max. number of nodes".
Scanning Mode
The selected setting affects the scanning of the logged-on clients.
The following settings are available:
All Channels
The client scans all permitted channels and selects the access point with the best
signal strength and connects to it.