To be the partner of your success
CONTENTS
MT5000/4000 SERIES HMI AND PLC CONNECTING GUIDE ........................................................- 1 -
1
SERIAL COMMUNICATION PIN DEFINITION ............................................................................................ - 1 -
2
PRINTER CONNECTING CABLE DIAGRAM ............................................................................................. - 3 -
2.1 Serial Interface Printer Cable ........................................................................................................- 3 -
2.2 Recommend Optional printer ........................................................................................................- 5 -
3
DOWNLOAD CABLE DIAGRAM .............................................................................................................. - 6 -
3.1 Download by Serial Port ...............................................................................................................- 6 -
3.2 Download by USB ........................................................................................................................- 6 -
3.3 Download by Network Ethernet ....................................................................................................- 6 -
4
COMMUNICATION SETTINGS AND GUIDE OF HMI CONNECTING WITH CONTROLLER ............................ - 8 -
4.1 ABB Corporation ...........................................................................................................................- 8 -
4.2 Allen-Bradley ..............................................................................................................................- 12 -
4.3 ACS-Tech80 Motion Controller ..................................................................................................- 24 -
4.4 ADAM .........................................................................................................................................- 26 -
4.5 AysjNet ........................................................................................................................................- 28 -
4.6 BACnet MS/TP ...........................................................................................................................- 29 -
4.7 Baldor NextMove ES (Motion Controller) ..................................................................................- 34 -
4.8 Barcode .......................................................................................................................................- 36 -
4.9 Baumuller
....................................................................................................................................- 37 -
4.10 Bosch Rexroth KVFC+ (Inverter) .............................................................................................- 38 -
4.11 Bosch Rexroth ...........................................................................................................................- 40 -
4.12 Bosch Rexroth Ethernet.............................................................................................................- 48 -
4.13 CANOpen Node Slave ..............................................................................................................- 54 -
4.14 Cimon ........................................................................................................................................- 61 -
4.15 Danfoss Inverter ........................................................................................................................- 63 -
4.16 Delta Corporation ......................................................................................................................- 69 -
4.17 Delta (Temperature Controller) .................................................................................................- 72 -
4.18 ENDA ........................................................................................................................................- 78 -
4.19 Emerson NetWork Power ..........................................................................................................- 80 -
4.20 Epower ......................................................................................................................................- 84 -
4.21 Facon Corporation .....................................................................................................................- 86 -
4.22 Fuji SPB ....................................................................................................................................- 91 -
4.23 GE Fanuc Automation Inc. ........................................................................................................- 93 -
4.24 HAIWELL ............................................................................................................................... - 102 -
4.25 HanG ....................................................................................................................................... - 104 -
4.26 Hitachi Inverter ....................................................................................................................... - 105 -
4.27 Hitachi IES Co., Ltd ................................................................................................................ - 107 -
4.28 Hollysys Corporation ................................................................................................
.............. - 114 -
4.29 HuaDA HD-JZ06 ..................................................................................................................... - 117 -
4.30 IDEC Corporation ................................................................................................................... - 119 -
4.31 Inovance Electric Corporation ................................................................................................. - 121 -
Vista de página 0
1 2 3 4 5 6 ... 381 382

Resumo do Conteúdo

Página 1 - CONTENTS

To be the partner of your success CONTENTS MT5000/4000 SERIES HMI AND PLC CONNECTING GUIDE ...- 1

Página 2

3 Download cable diagram HMI Ethernet terminalRJ45Ethernet Hub or SwitchRJ451 RX+(orange,white)4 BD4+ (bule)5 BD4- (bule,white)2 RX- (orange)3 T

Página 3

4 Communication settings and guide of HMI connecting with controller CSE925 CPX772 CPX782 CPX928 CPX935 CGR772 CGR935 PACSystem RX7i CPE010 CPE020 CRE

Página 4

4 Communication settings and guide of HMI connecting with controller GE SNP-X Protocol RS422 Communication NOTE: Set matching communication paramete

Página 5

4 Communication settings and guide of HMI connecting with controller ◎Network Communication Setting HMI: PLC: - 99 -

Página 6

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes System SC01-3

Página 7

4 Communication settings and guide of HMI connecting with controller Controller VersaMax terminal9 pin D-SUB (male)HMI terminal9pin D-SUB female/male

Página 8

4 Communication settings and guide of HMI connecting with controller HMI terminal9pin D-SUB female/male1 Rx-9 Tx+4Tx-12 SDA-7 GND13 SDB+5 GND6 Rx+11 R

Página 9 - 3 Download Cable Diagram

4 Communication settings and guide of HMI connecting with controller Haiwell RS485 communication ◎Supported Device Device Bit Address Word Address

Página 10 - Ethernet Hub or Switch

4 Communication settings and guide of HMI connecting with controller Analog Input ------- AI0-31 DD ◎Cable Diagram Haiwell RS232 communication cable C

Página 11

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes Password ---

Página 12 - RS232

4 Communication settings and guide of HMI connecting with controller ◎Communication Setting HMI default communication parameter: 4800, 7, none, 1; sta

Página 13

4 Communication settings and guide of HMI connecting with controller 4 Communication Settings and guide of HMI connecting with Controller Note:Do not

Página 14

4 Communication settings and guide of HMI connecting with controller Recount Motor Con ------ (0B)Recount Motor Cons 0 D Write only Store EEPROM --

Página 15 - 4.2 Allen-Bradley

4 Communication settings and guide of HMI connecting with controller H-1002(CPU2-10H) COMM-2H EH-150 EH-150(EH-CPU104) EH-150(EH-CPU104A) EH-150(EH-CP

Página 16 - ◎Serial System Communication

4 Communication settings and guide of HMI connecting with controller EH-150 EH-150(EH-CPU104) Serial port 1 on CPU Serial port 2 on CPU MICRO-EH

Página 17

4 Communication settings and guide of HMI connecting with controller HITACHI EHV Series Ethernet (TCP Slave) HMI Setting ◎Supported Device Hitachi

Página 18

4 Communication settings and guide of HMI connecting with controller Internal Output R 0000-FFFF ------ HHHH Data Area M 0000-FFFF ------ HHHH F

Página 19 - RSLogix5000 software setting

4 Communication settings and guide of HMI connecting with controller   The transmission speed of port 1 will be set with DIP 3, 4 switches o 3 on, 4

Página 20

4 Communication settings and guide of HMI connecting with controller DW ------ DW 0-FFF HHH FW ------ FW 0-BFF HHH SW ------ SW 0-BF HH ZW -----

Página 21

4 Communication settings and guide of HMI connecting with controller Hitachi EH-A23DR RS232 communication cable HMI terminal9pin D-SUB female/malecom2

Página 22

4 Communication settings and guide of HMI connecting with controller Series CPU Link Module COMM Type Parameter Cable Hollysys LM LM3109 RS232 on

Página 23

4 Communication settings and guide of HMI connecting with controller HMI Setting Note:In the dual redundancy system, just set one of IP addresses in

Página 24

4 Communication settings and guide of HMI connecting with controller RS485-2 ABB AC500 protocol: Default communication parameters 9600, 8, none, 1;

Página 25

4 Communication settings and guide of HMI connecting with controller ◎Cable Diagram Hollysys LM RS232 communication cable Controller port1 terminal9 p

Página 26 - PLC-5 RS232 cable diagram

4 Communication settings and guide of HMI connecting with controller RS485 communication ◎Supported Device Device Bit Address Word Address Fo

Página 27

4 Communication settings and guide of HMI connecting with controller RS485 Port HMI terminal9pin D-SUB female/male1 RX-6 RX+5 GNDcom0/com1Controller t

Página 28

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes Internal Rela

Página 29 - ADMA-4015

4 Communication settings and guide of HMI connecting with controller com0/com1HMI terminal9pin D-SUB female/maleController terminal8 pin Mini Din (mal

Página 30

4 Communication settings and guide of HMI connecting with controller RS422 RS485 PLC Setting - 122 -

Página 31 - 4.5 AysjNet

4 Communication settings and guide of HMI connecting with controller You should put off JP0, if communication on the COM0, RS485. You should set D8126

Página 32 - BACnet MS/TP

4 Communication settings and guide of HMI connecting with controller Device Bit Address Word Address Format Notes Input Relay X 000-177 ------ O

Página 33

4 Communication settings and guide of HMI connecting with controller com0/com1Controller COM1RS485 terminalHMI terminal9pin D-SUB female/male1 RX-6 RX

Página 34

4 Communication settings and guide of HMI connecting with controller PLC Setting 1. The PLC has two ports: port0 and port1, port1 support RS232 and R

Página 35 - BACnet IP protocol

4 Communication settings and guide of HMI connecting with controller PLC Settings Related parameters settings refer to the communication equipment spe

Página 36

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes C_bit C_bit 0-25

Página 37 - Baldor NextMove ES

4 Communication settings and guide of HMI connecting with controller RS232 communication cable HMI terminal9pin D-SUB female/maleController port08 pi

Página 38

4 Communication settings and guide of HMI connecting with controller Analog inputs ------ AIW0-30 DD Analog outputs ------ AQW0-30 DD Intern

Página 39 - 4.8 Barcode

4 Communication settings and guide of HMI connecting with controller 4.34 Kinco Corporation ◎Serial Communication Series CPU Link Module Driver Ki

Página 40 - Baumuller

4 Communication settings and guide of HMI connecting with controller K306-24DR K306-24AT K306-24AR K306EX-24AT K306EX-24AR K308-40AR K308-40AT K308-40

Página 41

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes Discrete inpu

Página 42

4 Communication settings and guide of HMI connecting with controller Controller terminal9 pin D-SUB (male)com23 TX2 RX5 GND8 TX7 RX5 GNDcom0/com1HMI t

Página 43 - 4.11 Bosch Rexroth

4 Communication settings and guide of HMI connecting with controller RS422 on the CPU unit ◎System configuration Series CPU Link Module COMM Type Para

Página 44 - L40 Hardware Settings

4 Communication settings and guide of HMI connecting with controller ◎Supported Device EB-MOD2P-01 Device Bit Address Word Address Format Notes Int

Página 45 - PPC-R software setting

4 Communication settings and guide of HMI connecting with controller e.g. :3X_BIT1.0~~1.15--------------------PQW256(binary) PLC software setting Set

Página 46 - L40 software setting

4 Communication settings and guide of HMI connecting with controller ABB AC500 Device Bit Address Word Address Format PLC Register MB0.0—8191.7 -

Página 47

4 Communication settings and guide of HMI connecting with controller NOTE: the address of DP can’t be the same as MPI’s. Double click the address num

Página 48

4 Communication settings and guide of HMI connecting with controller (1) Setting ID of Profibus by switching 8-bit Dip(DIP1 is lowest bit, DIP8 is hi

Página 49

4 Communication settings and guide of HMI connecting with controller RS485-2 communication cable HMI terminal9pin D-SUB female\maleController Modbus t

Página 50

4 Communication settings and guide of HMI connecting with controller NOTE: If the servo controller to modify the station number, the servo power need

Página 51 - Bosch Rexroth L25 Ethernet

4 Communication settings and guide of HMI connecting with controller ◎Cable Diagram ED Series RS232 communication cable HMI terminal9pin D-SUB female

Página 52

4 Communication settings and guide of HMI connecting with controller 4.37 Kinco Master & Kinco Slave(Master/Slave Protocol Connection) ◎Serial

Página 53

4 Communication settings and guide of HMI connecting with controller ◎Cable Diagram HMI terminal9pin D-SUB female/maleController terminal9pin D-SUB f

Página 54

4 Communication settings and guide of HMI connecting with controller ◎Network System configuration Series CPU Link Module Connect Type Parameter

Página 55

4 Communication settings and guide of HMI connecting with controller Keyence KV-N60AT protocol Default communication parameters, 9600bps, 8,even, 1

Página 56

4 Communication settings and guide of HMI connecting with controller Keyence KV-5000 EtherNet Slave protocol HMI Setting PLC configuration 1. "E

Página 57 - 4.13 CANOpen Node Slave

4 Communication settings and guide of HMI connecting with controller HMI terminal9pin D-SUB female/maleController com2 terminal9 pin D-SUB (male)2 TXD

Página 58 - Parameters Setting

4 Communication settings and guide of HMI connecting with controller High speed counter ------ CTH_current0- 65534 DDDDD High speed counter ------ CTH

Página 59

4 Communication settings and guide of HMI connecting with controller Example, PLC which corresponds to R009, the touch screen address is R0.09; PLC w

Página 60

4 Communication settings and guide of HMI connecting with controller Internal auxiliary relay MR0-599.15 ------ DDD.DD Latch Relay LR0-199.15 --

Página 61

4 Communication settings and guide of HMI connecting with controller Series CPU Link Module COMM Type Parameter Cable KOYO DIRECT SM24-T RS232 o

Página 62

4 Communication settings and guide of HMI connecting with controller KOYO DL06 series RS422 communication setting ◎Cable Diagram KOYO SM24-T series

Página 63

4 Communication settings and guide of HMI connecting with controller HMI terminal9pin D-SUB female/maleControllerRs485 terminal1 RX-6 RX+5 GNDBAFGcom0

Página 64

4 Communication settings and guide of HMI connecting with controller 4.40 KTC Srdlink ◎Serial Communication Series CPU Link Module Driver SRD SRD2

Página 65

4 Communication settings and guide of HMI connecting with controller NOTE: Must modify communication parameter in the programming software. ◎Suppor

Página 66 - Danfoss

4 Communication settings and guide of HMI connecting with controller 4.41 KYL Slave ◎Serial Communication Series CPU Link Module Driver KYL Slave

Página 67 - Modbus RTU Protocol:

4 Communication settings and guide of HMI connecting with controller Show valve state LB15 ------ DD Group close instruction LB17 ------ DD Stai

Página 68

4 Communication settings and guide of HMI connecting with controller ◎Ethernet Communication (Direct Online Simulation disable) Series CPU Link Modu

Página 69 - showed by RW register

4 Communication settings and guide of HMI connecting with controller Lecom AB RS485 communication ◎Supported Device Refer to the PLC software for de

Página 70

4 Communication settings and guide of HMI connecting with controller Controller terminal9 pin D-SUB (male)com23 TX2 RX5 GND8 TX7 RX5 GNDcom0/com1HMI t

Página 71

4 Communication settings and guide of HMI connecting with controller Cnet ON, DIP1 to be OFF /38400 LS Master-K MODBUS RTU Switch the DIP2 to be ON,

Página 72 - DVP RS232 communication

4 Communication settings and guide of HMI connecting with controller RS485 communication PLC setting If click “Connect+Write+Run+Monitor Start”,

Página 73 - DVP RS485-2 communication

4 Communication settings and guide of HMI connecting with controller LS Master-K CPU Direct protocol HMI Setting Default communication: 38400, 8, none

Página 74

4 Communication settings and guide of HMI connecting with controller If click “Connect+Write+Run+Monitor Start”, it will give a “Cannot Change PLC Mo

Página 75 - Delta DTA_DTB

4 Communication settings and guide of HMI connecting with controller RS485-2 communication PLC Setting 1. “Tools”---“Network Manager” set communicat

Página 76 - Controller Setting

4 Communication settings and guide of HMI connecting with controller 2. Communicating in the OPR mode LS XGB CPU Direct HMI Setting Default communic

Página 77

4 Communication settings and guide of HMI connecting with controller LS GLOFA Cnet protocol Default communication: 9600, 8, none, 1; station: 0 HMI Se

Página 78

4 Communication settings and guide of HMI connecting with controller 2. Set the parameters of module Take G6L-CUEC for example, Open GMWIN, select

Página 79

4 Communication settings and guide of HMI connecting with controller PLC-5/40 PLC-5/40L PLC-5/60 PLC-5/60L CompactLogix 1769-L20 1769-L30 1769-L31 176

Página 80

4 Communication settings and guide of HMI connecting with controller The Slot No. is the I/O slot position where the communication module is. For exam

Página 81 - RS485 terminal

4 Communication settings and guide of HMI connecting with controller HMI Setting PLC Setting 1. Modify the parameters of PLC: “Tools””Enet Frame Ed

Página 82 - ENDA Controller Devices

4 Communication settings and guide of HMI connecting with controller 4. Download: “Online””Connect””Write” XGK-CPUE Setting HMI setting PLC setti

Página 83

4 Communication settings and guide of HMI connecting with controller 2. Double click the [ base 00 ], in the pop-up window [communication module Set

Página 84

4 Communication settings and guide of HMI connecting with controller ◎Supported Device LS Master-K CPU Direct Device Bit Address Word Address Form

Página 85 - Emerson EC10

4 Communication settings and guide of HMI connecting with controller LS Master K-cnet Device Bit Address Word Address Format Notes I/O Relay P 0.0-25

Página 86 - Emerson RS232 communication

4 Communication settings and guide of HMI connecting with controller Communication Register ------ N_ word 0-9999 DDDD Link Register ------ L_ word 0-

Página 87 - 4.20 Epower

4 Communication settings and guide of HMI connecting with controller Auxiliary Register ------ M 0-9999 DDDD I/O Register ------ P 0-9999 DDDD

Página 88 - 25 pin D-SUB (male)

4 Communication settings and guide of HMI connecting with controller Buffer Memory(Bit) MX0-131056 ------ DDDDD Output(Bit) QX0-1763 ------ DD

Página 89

4 Communication settings and guide of HMI connecting with controller Read Holding Registers ------- 3X 1-65535 DDDDD Read Input Registers ------- 4X

Página 90 - FACON FB RS232 communication

4 Communication settings and guide of HMI connecting with controller PLC Setting RSLogix500 software setting NOTE: Driver: DF1 Full Duplex; Err

Página 91

4 Communication settings and guide of HMI connecting with controller 6 TX2 RX3 GNDController terminal6pin Mini DIN(male)HMI terminal9pin D-SUB female/

Página 92

4 Communication settings and guide of HMI connecting with controller Controller terminal9pin D-SUB(male)4 RX7 TX5 GNDHMI terminal9pin D-SUB female/mal

Página 93 - FB RS232 communication cable

4 Communication settings and guide of HMI connecting with controller ServoOne junior Lust ETH on the CPU Lust Ethernet Slave ◎Serial System configu

Página 94 - 4.22 Fuji SPB

4 Communication settings and guide of HMI connecting with controller The way to change IP of Servo drive system Plug the 24-volt power supply on the

Página 95

4 Communication settings and guide of HMI connecting with controller Parameter b3 b2 b1 b0 Initial IP int 192 168 39 5 hex C0 A8 27 05 Modified I

Página 96 - GE Fanuc Series

4 Communication settings and guide of HMI connecting with controller D1 D2 l u Press key T2 of about 1s D1 D2 b 0 Press key T2 of about 1s D1 D2 b

Página 97 - SNP RS485 on port2

4 Communication settings and guide of HMI connecting with controller CDE34.008 Refer to the Controller software for details: DriveManager for c-line d

Página 98

4 Communication settings and guide of HMI connecting with controller HMI terminal 9pin D-SUB female/maleController terminal9 pin D-SUB (male)2 TXD3 RX

Página 99

4 Communication settings and guide of HMI connecting with controller Device Bit Address Word Address Format LW.B 8000.0-8999.15 -------- DDDD.DD

Página 100

4 Communication settings and guide of HMI connecting with controller RS485 PLC Setting 1.Open X_builder,New project,select PLC type(MC280) - 186 -

Página 101

4 Communication settings and guide of HMI connecting with controller PLC Setting RSLogix5000 software setting NOTE: Protocol: DF1 Point to Point; Err

Página 102

4 Communication settings and guide of HMI connecting with controller 2.Open System block→Comm Port,set comm port(support Modbus) (1)Port0 setting(RS

Página 103 - ◎Cable Diagram

4 Communication settings and guide of HMI connecting with controller Notes:Using X_builder,Main routine cannot be empty ◎ Supported Device Device Bi

Página 104 - CMM311 RS422 communication

4 Communication settings and guide of HMI connecting with controller HMI接线端9pin D-SUB female/maleController port0接线端8 pin Mini Din (male)5 TXD4 RXD3

Página 105 - Haiwell RS232 communication

4 Communication settings and guide of HMI connecting with controller PLC Setting ◎Supported Device Device Bit Address Word Address Format Input

Página 106 - Haiwell RS485 communication

4 Communication settings and guide of HMI connecting with controller ◎Cable Diagram RS232 Communication HMI terminal9pin D-SUB female\maleController

Página 107 - ◎Communication Setting

4 Communication settings and guide of HMI connecting with controller RS485-2 Communication: ◎Supported Device Device Bit Address Word Address For

Página 108 - Hitachi SJ300

4 Communication settings and guide of HMI connecting with controller Users need to make the communication cable for M3 and HMI (region of red marquee

Página 109 - Inverter internal setting

4 Communication settings and guide of HMI connecting with controller FX1NC FX2N FX2NC FX□□-422-BD*3 FX□□-485-BD*3 FX□□-485-ADP*3 Mitsubishi FX0N/1N/2N

Página 110 - Hitachi

4 Communication settings and guide of HMI connecting with controller NOTE: 1. *1 The protocol support multi-station 2. *2 The protocol don’t support m

Página 111 - ◎Serial System configuration

4 Communication settings and guide of HMI connecting with controller FX2NC FX□□-485-ADP FX□□-232-BD RS232 Setting Your owner cable FX2N-10GM FX2N-20G

Página 112 - Port 2 on CPU

To be the partner of your success 4.32 Invt ...

Página 113

4 Communication settings and guide of HMI connecting with controller NOTE: Define the new device in the RSLogix5000 before using the register in the

Página 114 - - 111

4 Communication settings and guide of HMI connecting with controller Q01CPU Q02CPU Q02HCPU Q06HCPU Q12HCPU Q25HCPU Q03UDECPU Q04UDEHCPU Q06UDEHCPU Q13

Página 115 - - 112

4 Communication settings and guide of HMI connecting with controller HMI Setting When using the Mitsubishi FX1S、Mitsubishi FX0N/1N/2N/3G、Mitsubishi

Página 116

4 Communication settings and guide of HMI connecting with controller PLC Setting Select the “Operate communication setting” NOTE: 1. FX0N series d

Página 117 - ◎Serial System Configuration

4 Communication settings and guide of HMI connecting with controller D8120 Communication format D8121 Station number D8129 Overtime For example The

Página 118 - RS485-2

4 Communication settings and guide of HMI connecting with controller Mitsubishi Q00J (CPU Port) protocol HMI Setting Default parameters: 19200, 8, od

Página 119

4 Communication settings and guide of HMI connecting with controller HMI Setting Default parameters :115200, 8, odd, 1 ; Station No. : 0(Non-support s

Página 120 - RS232 communication

4 Communication settings and guide of HMI connecting with controller The differences of Mitsubishi Q_QnA (Link Port)、Mitsubishi Melsec Q: 1. Mitsubis

Página 121 - RS232 Port

4 Communication settings and guide of HMI connecting with controller b. Click “type” to select “intelligent” c. Click “switch setting” and set - 20

Página 122 - RS485 Port

4 Communication settings and guide of HMI connecting with controller Setting the intelligent function unit switch switch content example Switch1 CH

Página 123

4 Communication settings and guide of HMI connecting with controller If the communcation parameters of CH1 232 is 19200/8/odd/1, station:0, set as

Página 124 - Inovance H2u protocol

4 Communication settings and guide of HMI connecting with controller Example: Build a new tag whose name is a, the Data Type is INT: Note: 1. For the

Página 125 - PLC Setting

4 Communication settings and guide of HMI connecting with controller NOTE:Data fomat of PORT number is decimalism PLC Setting FX3GE-24M 1. D

Página 126 - PLC setting

4 Communication settings and guide of HMI connecting with controller NOTE: Data fomat of PORT number is decimalism FX3U-ENET-L 1. Open“FX3U-ENET-

Página 127

4 Communication settings and guide of HMI connecting with controller 3. Click“Open settings”,the parameters configuration as follow: NOTE: Data fom

Página 128

4 Communication settings and guide of HMI connecting with controller PLC Setting 1. Network parameters [network type] select "Ethernet";

Página 129

4 Communication settings and guide of HMI connecting with controller "1"; [Group number] range is 0-32, select "0"; [station numbe

Página 130

4 Communication settings and guide of HMI connecting with controller Mitsubishi QnA 3EBin Ethernet(TCP Slave) protocol L02: HMI Setting NOTE: 1.

Página 131 - RS232 communication cable

4 Communication settings and guide of HMI connecting with controller Click “Open Setting”, the parameters configuration as follow: NOTE: Host Stati

Página 132 - RS485 communication cable

4 Communication settings and guide of HMI connecting with controller NOTE: 1. PLC station number must be 255 2. Data format of Port number is decim

Página 133 - Kinco PLC Series

4 Communication settings and guide of HMI connecting with controller NOTE: Host Station Port No. will be set by the selected format. ◎Supported Devic

Página 134

4 Communication settings and guide of HMI connecting with controller State S 000-999 ------ DDD Timer Value ------ T_word 000-255 DDD Counter Val

Página 135

4 Communication settings and guide of HMI connecting with controller Note: 1. The File Number is unique, a same File Number cannot map to different Na

Página 136

4 Communication settings and guide of HMI connecting with controller Counter Value ------ C_dword200-255 DDD 32 bit device Q00jCPU Device Bit Addre

Página 137

4 Communication settings and guide of HMI connecting with controller Timer Contact TS 0-511 ------ DDDD Link Relay B 0-7FF HHHH Edge Relay V 0-1023

Página 138

4 Communication settings and guide of HMI connecting with controller Q_QnA(link port) Device Bit Address Word Address Format Special Link Relay SB00

Página 139 - Project configuration

4 Communication settings and guide of HMI connecting with controller Special Data Register ------ SD 0000-2047 DDDD Mitsubishi QJ71E71 EtherNet Slave

Página 140 - - 137

4 Communication settings and guide of HMI connecting with controller Step Coil SC 0-2047 ------ DDDD Step Contact SS 0-2047 ------ DDDD Timer Coil T

Página 141 - RS485-4 communication cable

4 Communication settings and guide of HMI connecting with controller Latch Relay L 0-8191 ------ DDDD Special Internal Relay SM 0-2047 ------ DDDD I

Página 142 - Kinco Servo Series

4 Communication settings and guide of HMI connecting with controller com0/com1HMI terminal9pin D-SUB female/male1 RX-6 RX+5 GND4Tx-7Tx+3GND1Rx-2Rx+4 T

Página 143

4 Communication settings and guide of HMI connecting with controller com0/com1HMI terminal9pin D-SUB female/male2 RX3 TX2 TXD1 RXD5 GND3 GNDController

Página 144

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes Relay CB 00-

Página 145 - Kinco Slave

4 Communication settings and guide of HMI connecting with controller 4.51 Modbus ◎Serial Communication Series CPU Link Module SIO type Driver Modb

Página 146 - Keyence KV-3000

4 Communication settings and guide of HMI connecting with controller AB CompactLogix/ControlLogix Series Ethernet(TCP Slave) protocol HMI Setting P

Página 147 - - 144

4 Communication settings and guide of HMI connecting with controller NOTE: 1. Modbus RTU protocol supports broadcasting station number, but the rad

Página 148 - - 145

4 Communication settings and guide of HMI connecting with controller Modbus RTU MT500 compatible protocol RS232 communication Default communicatio

Página 149 - KV-16DT

4 Communication settings and guide of HMI connecting with controller Modbus TCP protocol Network configuration Modbus UDP protocol Network config

Página 150 - KV-3000

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Modbus RTU Device Bit Address Word Address Format Notes Ou

Página 151 - KV-N60AT

4 Communication settings and guide of HMI connecting with controller 12 3 4 5 6 7 84X-DINV(2word)H4X(2word)5 6781 234 H5X(2word)7 8 5 63 412 HH Lbyte

Página 152 - Koyo Direct

4 Communication settings and guide of HMI connecting with controller Data relay 4X_bit 1.00-65535.15 ------ DDDDD.DD Input Register ------ 3X

Página 153 - PLC software setting

4 Communication settings and guide of HMI connecting with controller System configuration Series CPU Link Module COMM Type Parameter Cable MODROL

Página 154

4 Communication settings and guide of HMI connecting with controller 4.53 OE MAX ◎Serial Communication Series CPU Link Module Driver NX7 NX7 RS23

Página 155 - 9pin D-SUB female/male

4 Communication settings and guide of HMI connecting with controller General Register ------ W_word 0-2047 DDDD Special Register ------ SR_word 0-511

Página 156 - KTC RS485-2 communication

4 Communication settings and guide of HMI connecting with controller C2000H C1000HF C500-LK201-V1 C500-LK203 C20H/28H/40H Link I/F on the CPU unit C2

Página 157

4 Communication settings and guide of HMI connecting with controller Output data file O0:0.0-255.15 ------ DD.DD Input data file I1:0.0-255.15 ----

Página 158 - 4.41 KYL Slave

4 Communication settings and guide of HMI connecting with controller CJ1G-CPU44H CJ1G-CPU43H CJ1G-CPU42H CJ1M-CPU23 CJ1M-CPU22 CJ1M-CPU21 CJ1M-CPU13 C

Página 159 - Lecom AB RS232 communication

4 Communication settings and guide of HMI connecting with controller CS1H CS1G CS1W-ETN21/EIP21 (UDP Slave) CJ1W-ETN21/EIP21 CJ2H-***-EIP SYSMAC NJ N

Página 160 - Lecom AB RS485 communication

4 Communication settings and guide of HMI connecting with controller CS1G-CPU45H CS1G-CPU44H CS1G-CPU43H CS1G-CPU42H CS1G-CPU45-V1 CS1G-CPU44-V1 CS1G-

Página 161

4 Communication settings and guide of HMI connecting with controller ◎Serial Communication Setting OMRON CP Series Host Link protocol HMI Setting Defa

Página 162 - LS Master-K Cnet protocol

4 Communication settings and guide of HMI connecting with controller 5 ON: communication port2,Toolbus(default) OFF:Port 2 communications settings acc

Página 163 - RS485 communication

4 Communication settings and guide of HMI connecting with controller NOTE: Select custom communication parameters (non-standard communication paramet

Página 164 - - 161

4 Communication settings and guide of HMI connecting with controller ◎Network Communication Setting OMRON CJ Series Ethernet(TCP Slave) HMI Setting

Página 165 - - 162

4 Communication settings and guide of HMI connecting with controller 2. Double-click the Ethernet communication module, set the parameters OMRON CJ

Página 166 - RS485-2 communication

4 Communication settings and guide of HMI connecting with controller Attention: HMI and PLC must be set in the same network,while the node ID should

Página 167 - LS XGB CPU Direct

4 Communication settings and guide of HMI connecting with controller 5. Set the Network number and Node ID (1)Network number (2)You can change the

Página 168 - - 165

4 Communication settings and guide of HMI connecting with controller Note: *1 Variable less than three address the need to fill the former 0 The cor

Página 169 - - 166

4 Communication settings and guide of HMI connecting with controller PLC Setting Type in IE the IP address(ex:http://192.168.11.33/C00.HTM)and the p

Página 170 - - 167

4 Communication settings and guide of HMI connecting with controller Omron C Series Host Link Device Bit Address Word Address Format Hold Relay HR_bi

Página 171

4 Communication settings and guide of HMI connecting with controller Device Bit Address Word Address Format Channel I/O CIO 0000.00-6143.15 -----

Página 172 - XGK-CPUE Setting

4 Communication settings and guide of HMI connecting with controller 0.00-6143.15 CIO_FORCE ------ CIO_FORCE_RELEASE ------ CIO_RELEASE_STATUS -

Página 173 - - 170

4 Communication settings and guide of HMI connecting with controller Channel IO 0.00-6143.15 CIO_bit ------ DDDD.DD CIO_FORCE ------ CIO_FORCE_RELE

Página 174

4 Communication settings and guide of HMI connecting with controller Controller terminal9pin D-SUB(male)3 RD2 SD9 GND4 RTS5 CTSHMI terminal9pin D-SUB

Página 175 - - 172

4 Communication settings and guide of HMI connecting with controller HMI terminal9pin D-SUB female/male1 RX-6 RX+5 GNDSDA-SDB+FGRDA-RDB+4 TX-9 TX+Cont

Página 176 - - 173

4 Communication settings and guide of HMI connecting with controller ◎Communication Setting Default communication: 9600, 7, even, 2; station: 0 ◎Supp

Página 177 - - 174

4 Communication settings and guide of HMI connecting with controller 3 AT execute/stop 00:stop 01:AT execute 4 write-in mode 00:save 01:RAM 5 RAM

Página 178 - LS iG5A protocol

4 Communication settings and guide of HMI connecting with controller Series CPU Link Module Connect Type Parameter Cable OPTO 22 SNAP-UP1-ADS E

Página 179

4 Communication settings and guide of HMI connecting with controller Integer data file ------ INT000000~254255 DDDDDD*1 DInteger data file ------ DI

Página 180 - 5 GND 3 GND

4 Communication settings and guide of HMI connecting with controller Tune I Float Tune D Float Mode Double IN BIT QN BIT PIN Float PQN Float NT

Página 181 - RS422 communication cable

4 Communication settings and guide of HMI connecting with controller 4.57 Panasonic Electric Corporation ◎Serial Communication Series CPU Link Modul

Página 182

4 Communication settings and guide of HMI connecting with controller FP2SH RS232C port on the Control unit Your owner cable AFP2462 AFP2465 AFP2803 A

Página 183 - - 180

4 Communication settings and guide of HMI connecting with controller RS422 communication ◎Supported Device FP Series Device Bit Address Word Addre

Página 184 - - 181

4 Communication settings and guide of HMI connecting with controller Link Relay WL0~32767 DDDDD File Register FL0~99999 DDDDD NOTE: 1. Exa

Página 185

4 Communication settings and guide of HMI connecting with controller HMI terminal9pin D-SUB female/malecom23 TX2 RX5 GND8 TX7 RX5 GNDcom0/com1Controll

Página 186 - ServoOne junior

4 Communication settings and guide of HMI connecting with controller Parker Compax3 Compax3 RS232 on CPU unit Parker Compax3 RS485 on CPU unit Parker

Página 187 - 4.45 Memory map

4 Communication settings and guide of HMI connecting with controller PLC Setting NOTE: RS-485 Settings can be made in the C3 Servo Manager under “RS4

Página 188

4 Communication settings and guide of HMI connecting with controller Parker 6K protocol Default communication parameters: 9600, 8, 1, none; station:

Página 189

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Parker Compax3 Device Bit Address Word Address Format R_Bit 0

Página 190 - - 187

4 Communication settings and guide of HMI connecting with controller com23 TX2 RX5 GND8 TX7 RX5 GNDcom0/com1HMI terminal9pin D-SUB female/male2 TXD3 R

Página 191 - ◎ Cables Production

4 Communication settings and guide of HMI connecting with controller TAS_Bit 1.01-2.32 ------ TSS_Bit 1-32 ------ TIN_Bit 1.01-3.32 -

Página 192

4 Communication settings and guide of HMI connecting with controller com0/com1HMI terminal9pin D-SUB female/maleControllerRS485 terminal1 RX-6 RX+3 T

Página 193

4 Communication settings and guide of HMI connecting with controller 4.59 PMAC Motion Controller ◎Serial Communication Series CPU Link Module Driv

Página 194

4 Communication settings and guide of HMI connecting with controller Run current program ------ RUN 0-9999 DDDD W Halt program ------ HLT 0-9999 DDDD

Página 195

4 Communication settings and guide of HMI connecting with controller AURORA PVI-6000-OUTD-US-W RS485 on the port Aurora PV ◎System configuration Se

Página 196

4 Communication settings and guide of HMI connecting with controller com0/com1HMI terminal9pin D-SUB female/maleControllerRS485 terminal1 Rx-(A)6 Rx+(

Página 197 - - 194

4 Communication settings and guide of HMI connecting with controller NOTE:Input and Output Modules should match with Master Configuration. PLC Sett

Página 198 - NOTE: 1. *

4 Communication settings and guide of HMI connecting with controller (4) Right click,choose “Insert Object” C

Página 199 - - 196

4 Communication settings and guide of HMI connecting with controller (6) Profibus DP Slave has adaption function,you can change the transmission rate

Página 200

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes Direct I/O

Página 201

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes Linear Decele

Página 202

4 Communication settings and guide of HMI connecting with controller Series CPU Link Module Driver RF-IC RF-IC RS232 on the CPU unit RF-IC ◎Syst

Página 203 - RS422 communication

4 Communication settings and guide of HMI connecting with controller ◎System configuration Series CPU Link Module COMM Type Parameter Cable RKC C

Página 204 - - 201

4 Communication settings and guide of HMI connecting with controller 4 7 even 1 5

Página 205 - - 202

4 Communication settings and guide of HMI connecting with controller HMI CAN terminal9pin D-SUB female2 CAN_L7 CAN_H2 CAN_L7 CAN_HController CAN term

Página 206

4 Communication settings and guide of HMI connecting with controller RS485 communication ◎Supported Device Device Bit Address Word Address Format Not

Página 207 - - 204

4 Communication settings and guide of HMI connecting with controller com0/com1ControllerRS485 terminalHMI terminal9pin D-SUB female/male1 RX-X1-1X1-26

Página 208 - - 205

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes Channel Sampl

Página 209

4 Communication settings and guide of HMI connecting with controller TSX 37 10 028DR1 TSX 37 21 101 TSX 37 22 101 TSX 37 21 001 TSX 37 22 001 Premium

Página 210 - FX3GE-24M

4 Communication settings and guide of HMI connecting with controller TSX3705001 TSX3705001 TSX 37 05 028DR1 TSX 37 08 056DR1 TSX 37 10 128DT1 TSX 37 1

Página 211 - FX3U-ENET-L

4 Communication settings and guide of HMI connecting with controller Modbus RTU protocol Default communication:9600, 8, even, 1; station: 1 RS232

Página 212

4 Communication settings and guide of HMI connecting with controller HMI terminal9pin D-SUB female/maleController terminal9 pin D-SUB (male)3 TXD2 RXD

Página 213

4 Communication settings and guide of HMI connecting with controller PLC Setting PL7 software setting 1. Start menu“modicum telemecanique”  “XWAY D

Página 214 - - 211

4 Communication settings and guide of HMI connecting with controller 4. And then click ”XWAY Test””Connect”, if the connection is successful,

Página 215

4 Communication settings and guide of HMI connecting with controller Modbus RTU protocol setting as follow: 6. Setting up the configuration and do

Página 216

4 Communication settings and guide of HMI connecting with controller RS485 communication PLC Setting 1. Specify a large number for the internal word

Página 217

4 Communication settings and guide of HMI connecting with controller 2. You must program a coil with maximum address to open the memory area for th

Página 218

4 Communication settings and guide of HMI connecting with controller PLC software setting: “Hardware Configuration”double click “Ccom” to select “MOD

Página 219 - - 216

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format State instructions(W

Página 220 - - 217

4 Communication settings and guide of HMI connecting with controller 14H SC_L Read PV lower limit side scaling 15H SC_H Read PV higher limit sid

Página 221 - - 218

4 Communication settings and guide of HMI connecting with controller 4.68 SIEMENS ◎Serial Communication Series CPU Link Module Driver S7-200 CPU2

Página 222 - - 219

4 Communication settings and guide of HMI connecting with controller CPU314IFM CPU315 CPU315-2 DP CPU316 CPU316-2 DP CPU318-2 NOTE 1. *1 :The proto

Página 223 - - 220

To be the partner of your success 4.76 Trio motion controller ...

Página 224 - - 221

4 Communication settings and guide of HMI connecting with controller Note: PLC station must match with the ADAM-4015 configuration. PLC Setting Conne

Página 225 - FX Series RS422 Cable

4 Communication settings and guide of HMI connecting with controller ◎BUS Communication Please refer to 4.59 Profibus DP Slave. ◎Serial System configu

Página 226 - Q02U Series RS232 Cable

4 Communication settings and guide of HMI connecting with controller SIMATIC S7-200 CPU222 CPU224 CPU224 XP CPU226 CP 243-1 IT CP 243-1 Ethernet Setti

Página 227 - Q Series RS485/422 Cable

4 Communication settings and guide of HMI connecting with controller PLC Setting SIEMENS S7-300/400 (PC Adapter Direct) protocol HMI Setting Defaul

Página 228

4 Communication settings and guide of HMI connecting with controller NOTE: 1. If you use MT5-S7-300 adapter to communicate, the baudrate of PLC must

Página 229

4 Communication settings and guide of HMI connecting with controller 3. After the software change, downloaded to PLC, make sure the transmission rate

Página 230 - - 227

4 Communication settings and guide of HMI connecting with controller SIEMENS S7-300/400 (MPI Direct) protocol HMI Setting NOTE: 1. This protocol i

Página 231 - - 228

4 Communication settings and guide of HMI connecting with controller 2. This protocol supports multi-station communication, and the MPI is RS485 port,

Página 232 - - 229

4 Communication settings and guide of HMI connecting with controller PLC setting PLC station No. can be 2-15, MPI baud rate can be 19.2k or 187.5k

Página 233 - Modbus RTU Extend

4 Communication settings and guide of HMI connecting with controller PLC Setting The settings for the CP 243-1 are defined in STEP 7 Micro/WIN via th

Página 234 - - 231

4 Communication settings and guide of HMI connecting with controller 3. Specifying IP address 3.0 Define an IP address for the CP 243-1. Caution:The

Página 235 - Ethernet communication cable

4 Communication settings and guide of HMI connecting with controller Read Version ——— Version 0-65535 DDDDD Read Module Name ——— Name 0-65535 DDDDD No

Página 236 - MODROL RS485

4 Communication settings and guide of HMI connecting with controller 5. Configuration connection 7.0 The configuration for connecting the CP 243-1

Página 237 - 4.53 OE MAX

4 Communication settings and guide of HMI connecting with controller 7. Assigning memory 11.0 Specify a memory area for the configuration of the CP

Página 238 - 4.54 Omron Corporation

4 Communication settings and guide of HMI connecting with controller 9. Confirm message 13.0 Click “Yes” to confirm the message that appears. 10.

Página 239 - - 236

4 Communication settings and guide of HMI connecting with controller SIEMENS S7-1200 Ethernet(TCP Slave) protocol HMI Setting PLC Setting 1. Modif

Página 240 - ◎Network Communication

4 Communication settings and guide of HMI connecting with controller c. Select the device, press “Load”. 2. Build the data block Data block must be c

Página 241

4 Communication settings and guide of HMI connecting with controller NOTE: 1. Make sure the data type of PLC same as the HMI when defining the data b

Página 242 - CS1W-SCB41

4 Communication settings and guide of HMI connecting with controller 1. In “HW configuration” insert CP300 industrial Ethernet. 2. Set IP address in

Página 243

4 Communication settings and guide of HMI connecting with controller NOTE: Dual redundant parameters configuration of S7-400 Ethernet communication

Página 244 - - 241

4 Communication settings and guide of HMI connecting with controller PLC Setting 1. In the hardware configuration, insert CP400 Ethernet module CP443-

Página 245 - - 242

4 Communication settings and guide of HMI connecting with controller V Relay V.B 0.0-10238.7 ------ DDDDD.O Internal Memory Relay M.B 0.0-31.7 -----

Página 246

4 Communication settings and guide of HMI connecting with controller ◎Communication Setting ◎Supported Device Device Bit Address Word Address Form

Página 247

4 Communication settings and guide of HMI connecting with controller SIEMENS S7-300/400 (PC Adapter Direct) Device Bit Address Word Address Format

Página 248

4 Communication settings and guide of HMI connecting with controller bit) Data Register Relay ------ DBn_DBW 100000-409665534 DDDDDDDDD n:1~4096 Dat

Página 249

4 Communication settings and guide of HMI connecting with controller 2. DBn_DBX, DBn_DBW, DBn_DBD is a custom block. First three data formats for data

Página 250

4 Communication settings and guide of HMI connecting with controller External Input node I 0.0~255.7 ------ DDD.O External Output node Q 0.0~255.7

Página 251 - - 248

4 Communication settings and guide of HMI connecting with controller PC/PPI Cable switch to select the baud rate Baud SWITCH(1=on) 38400 000 19200 0

Página 252 - - 249

4 Communication settings and guide of HMI connecting with controller PC / PPI cable on the baud rate DIP switch settings, you must set the baud rate w

Página 253 - - 250

4 Communication settings and guide of HMI connecting with controller Ethernet communication protocol cable Cross-connection or crossover network cabl

Página 254 - RS232 Communication Cable

4 Communication settings and guide of HMI connecting with controller PLC Setting Please reference to controller manual. ◎Supported Device Device Bit

Página 255 - RS422 Communication Cable

4 Communication settings and guide of HMI connecting with controller RS485 ◎ Supported Device Device Bit Address Word Address Format Notes Inp

Página 256

4 Communication settings and guide of HMI connecting with controller State S 000-999 ------ DDD Timer Value ------ T_word 000-255 DDD Counter Val

Página 257 - OMRON E5EZ-R3

4 Communication settings and guide of HMI connecting with controller BACnet IP Ethernet interface on CPU BACnet IP ◎Serial System configuration Se

Página 258 - OPTO 22 SNAP Ethernet(TCP)

4 Communication settings and guide of HMI connecting with controller Default communication: 19200, 8, none, 1; station: 1 RS232 communication RS485 c

Página 259 - Register

4 Communication settings and guide of HMI connecting with controller Counter(Current value) ------ C_Current_Word 0-199 DDD Counter ------ C_Curre

Página 260

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Please refer to TMCL Reference Manual for device details TMCM_

Página 261 - Panasonic FP

4 Communication settings and guide of HMI connecting with controller GIO 0.0-0.10 2.0-2.07 1.0-1.7 DDD.DD Read Only CALC ------ 0-9 D Write Only

Página 262

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes Internal Rela

Página 263

4 Communication settings and guide of HMI connecting with controller S0~S1023 0X 20481~0X 21504 M8000~M8511 0X 24577~0X 25088 T0~T618 0X 25601~0X 2

Página 264 - Tool port:

4 Communication settings and guide of HMI connecting with controller D3CellTM D3CellTM RS485 on the CPU unit RS422 Setting Your owner cable ◎Su

Página 265

4 Communication settings and guide of HMI connecting with controller ◎Network Communication Setting HMI setting TCXMAIN1: S2PU72A: PLC setting -

Página 266 - Parker Compax3 protocol

4 Communication settings and guide of HMI connecting with controller Please refer to the communication equipment related documentation to set the para

Página 267 - Parker SLVD Series protocol

4 Communication settings and guide of HMI connecting with controller 0x6C000000-0x6C003FFF R6C_B 0.00-3FFF.1F ------ HHHH.HH 0x6D000000-0x6D003FFF

Página 268 - Parker ACR9000 protocol

4 Communication settings and guide of HMI connecting with controller PLC Setting Please refer to the communication equipment related documentation t

Página 269

4 Communication settings and guide of HMI connecting with controller 0x6A000000-0x6A003FFF ------ R6A 0-3FFF HHHH 0x6B000000-0x6B003FFF ------ R6B

Página 270 - Parker Compax3 Series

4 Communication settings and guide of HMI connecting with controller Controller internal setting: RS485-4 communication Controller internal settin

Página 271 - 6k/9000 Series

4 Communication settings and guide of HMI connecting with controller Trio controller setting: SETCOM(baudrate, databits, stopbits, parity, port, 5) SE

Página 272

4 Communication settings and guide of HMI connecting with controller ADDRESS=1 SETCOM(9600,8,1,2,1,4) ◎Supported Device TRIO Device Bit Address Word

Página 273

4 Communication settings and guide of HMI connecting with controller HMI terminal9pin D-SUB female/maleController B port terminal 8 pin Mini Din (male

Página 274

4 Communication settings and guide of HMI connecting with controller RS485 default communication: 57600, 8, 1, none; station: 64 PLC Setting 1. COM

Página 275

4 Communication settings and guide of HMI connecting with controller 2. Initialize ID, and program as below, download to controller. 3. Change the j

Página 276

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes Inputs I 0~99

Página 277 - - 274

4 Communication settings and guide of HMI connecting with controller Ethernet communication protocol cable Cross-connection or crossover network cab

Página 278 - - 275

4 Communication settings and guide of HMI connecting with controller Device Bit Address Word Address Format Notes send LB 0 ------ D

Página 279 - A-type violet cable

4 Communication settings and guide of HMI connecting with controller PLC Setting Please refer to the communication equipment related documentation to

Página 280

4 Communication settings and guide of HMI connecting with controller NOTE:CP1* baudrate 19200bps. *:CP1 programming port is USB(RS232). ◎Supported De

Página 281

4 Communication settings and guide of HMI connecting with controller 3 RXD2 TXD1 GNDPLC Auxiliary interfaceJST 4PIN JST 4PIN com23 TX2 RX5 GND8 TX7 RX

Página 282

4 Communication settings and guide of HMI connecting with controller C FJOG ------ C 0 D D RJOG ------ D 0 D E Free halt ------ E0 D F

Página 283 - ◎Systems Configuration

4 Communication settings and guide of HMI connecting with controller ◎Communication Setting HMI Setting Yamatake DCP30 protocol Default communication:

Página 284 - PCS1.C8

4 Communication settings and guide of HMI connecting with controller PLC Setting 1. Set modbus RTU in the SLP-D10, and then download. 2. Station mat

Página 285

4 Communication settings and guide of HMI connecting with controller FBR2_R ------ 1.0-30.22 DDD.DD FBR3_R ------ 1.0-30.22 DDD.DD FBR4_R ---

Página 286

4 Communication settings and guide of HMI connecting with controller Sub addr DD correspond to temperature controller: Sub Addr Parameter Sub Addr Par

Página 287

4 Communication settings and guide of HMI connecting with controller Commutator terminal9 pin D-SUB male2 TX3 RX5 GNDcom23 TX2 RX5 GND8 TX7 RX5 GNDcom

Página 288

4 Communication settings and guide of HMI connecting with controller ∑Ⅱ /∑Ⅱ P lu s(Servo Controller) SGDM RS232 on the CPU unit Yaskawa SGDM RS422 on

Página 289

4 Communication settings and guide of HMI connecting with controller H5-01 Secondary station address 0~FFH Secondary station number 1F H5-02 The ch

Página 290

4 Communication settings and guide of HMI connecting with controller Analog Input ------ AI 0-65535 DDDDD Float Analog Output ------ AO 0-65535 DDDDD

Página 291 - - 288

4 Communication settings and guide of HMI connecting with controller RS485-4 communication PLC Setting Related parameters Settings refer to the

Página 292

4 Communication settings and guide of HMI connecting with controller NOTE: Station No. is a decimal number corresponding to axis address of servo co

Página 293

4 Communication settings and guide of HMI connecting with controller NOTE: 1. axis address 0020H is the station number of PLC,here is hexadecimal,HMI

Página 294

4 Communication settings and guide of HMI connecting with controller PLC Setting 1. Set the IP,connect with the MPE720 software 2. How to set the IP

Página 295 - 4.67 SHIMADEN FP23

4 Communication settings and guide of HMI connecting with controller Change, save, and save to flash: Restart the controller and the set is ok. If

Página 296

4 Communication settings and guide of HMI connecting with controller ◎Supported Device V inverter Device Bit Address Word Address Format Notes Intern

Página 297

4 Communication settings and guide of HMI connecting with controller SGDV Device Bit Address Word Address Format Function Selection ------------ (Pn00

Página 298 - SIEMENS S7-200

4 Communication settings and guide of HMI connecting with controller HMI terminal9pin D-SUB female/maleController terminal1 RX-6 RX+R-S+R+com0/com1S-

Página 299 - - 296

4 Communication settings and guide of HMI connecting with controller Ethernet communication protocol cable Cross-connection or crossover network cable

Página 300 - ◎BUS Communication

4 Communication settings and guide of HMI connecting with controller F3LC11-2N ◎Network Communication(direct online simulation disable) Series

Página 301 - SIEMENS S7-200 protocol

4 Communication settings and guide of HMI connecting with controller ControllerRS485 terminalHMI terminal9pin D-SUB female/male- +com0/com11 RX-6 RX+

Página 302

4 Communication settings and guide of HMI connecting with controller F3SP20-0N F3SP21-0N F3SP25-2N F3SP28-3N F3SP30-0N F3SP35-5N F3SP38-6N F3SP53-4H

Página 303

4 Communication settings and guide of HMI connecting with controller RS485-4 default communication: 19200, 8, 1, none; station: 1 RS485-2 default c

Página 304 - - 301

4 Communication settings and guide of HMI connecting with controller PLC Setting RS485-4 communication configuration Set the 485 communication modul

Página 305

4 Communication settings and guide of HMI connecting with controller 8 OFF Always OFF 3. Station No. setting 1 4. Set the termination resistance swi

Página 306 - HMI setting

4 Communication settings and guide of HMI connecting with controller Index Register ------ V_word 1~64 DD File Register ------ B_word 1~256 DD

Página 307 - - 304

4 Communication settings and guide of HMI connecting with controller AI AI-518 AI-701 RS485 on the CPU unit YuDian AI Single_Loop AI-7048 RS485 on t

Página 308

4 Communication settings and guide of HMI connecting with controller NOTE: 1、When setting the parameter of ADDR, it match the PLC Station Number . 2、I

Página 309 - - 306

4 Communication settings and guide of HMI connecting with controller 1 HIAL HIAL HIAL HIAL 2 LoAL LoAL LoAL LoAL 3 dH

Página 310 - - 307

4 Communication settings and guide of HMI connecting with controller 40 C08 C08 41 t08 t08 42 C09 C09 43-85 t09-C30 t09-C3

Página 311 - - 308

4 Communication settings and guide of HMI connecting with controller 30 1EH PHIA 31 1FH PLoA 32 20H ALP 33 21H FSb 34 22H

Página 312

4 Communication settings and guide of HMI connecting with controller ◎Supported Device - 35 -

Página 313

4 Communication settings and guide of HMI connecting with controller ◎Network System configuration Series CPU Link Module COMM Type Parameter Cab

Página 314 - - 311

4 Communication settings and guide of HMI connecting with controller (3)Update and get configuration: After finish the system basic configuration

Página 315

4 Communication settings and guide of HMI connecting with controller (4)Click icon after updating controller configuration, then it will pop upWinE

Página 316

4 Communication settings and guide of HMI connecting with controller (Only data of comms can be monitored, some address greater than or equal to 100 a

Página 317 - - 314

1 Serial Communication Pin definition MT5000/4000 Series HMI and PLC connecting guide 1 Serial Communication Pin definition  Serial port COM0 COM0 i

Página 318

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes Word -------

Página 319 - - 316

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes Bit type DB_B

Página 320 - NOTE:

4 Communication settings and guide of HMI connecting with controller ◎Communication Setting ◎Supported Device Device Bit Address Word Address Form

Página 321 - - 318

4 Communication settings and guide of HMI connecting with controller 4.11 Bosch Rexroth ◎Serial Communication Series CPU Link Module Driver PPC-R

Página 322 - - 319

4 Communication settings and guide of HMI connecting with controller NOTE: To communicate with the touch screen, declare variable firstly in the Rexr

Página 323

4 Communication settings and guide of HMI connecting with controller PLC Setting PPC-R software setting PLC connects with PC via crossover ethernet

Página 324 - - 321

4 Communication settings and guide of HMI connecting with controller 3. “Resource”--->“Global variables”--->declare variable in “HMI” 4. Click

Página 325 - SIEMENS MPI protocol

4 Communication settings and guide of HMI connecting with controller NOTE:Must select Download symbol file Click “OK” and pop-up the window as follo

Página 326 - 4.69 SIKO AG05 SIKONETZ5

4 Communication settings and guide of HMI connecting with controller Input B0 and pop-up the dialog, configurations as follows, click “OK”: And set u

Página 327

4 Communication settings and guide of HMI connecting with controller Setting communication parameter: Then click “Login”: Communicating successfull

Página 328 - RS485

1 Serial Communication Pin definition 4 NC -- 5 SG Signal ground 6 NC -- 7 RXD Receive data 8 TXD Transmit data 9 NC -- The COM2 can be

Página 329 - 4.71 TAIAN

4 Communication settings and guide of HMI connecting with controller NOTE:The PLC panel must be set up, press” Enter”, then press” △”, un

Página 330

4 Communication settings and guide of HMI connecting with controller com0/com1Controller terminal15 pin D-SUB (male)HMI terminal9pin D-SUB female/male

Página 331 - 4.72 TMCM_303

4 Communication settings and guide of HMI connecting with controller ※P L C A ttr ib u te (station disable) ※N etw ork con figu ration(Note: PLC

Página 332 - TMCM_303

4 Communication settings and guide of HMI connecting with controller At this time open “indralogic” -->“online/communication parameter” -->“ne

Página 333 - THINGET Controller protocol

4 Communication settings and guide of HMI connecting with controller 2. “Resource”--->“Global variables”--->declare variable in “HMI” 3. Click

Página 334 - MODBUS RTU protocol

4 Communication settings and guide of HMI connecting with controller PLC Setting 1. Modify the IP in the controller. 2. Declare variable in controlle

Página 335 - 4.74 Toledo DLoadCell

4 Communication settings and guide of HMI connecting with controller 2 ) IN Insert IndraMotion MLC L25 properties box, set the Firmware release (FWA-C

Página 336 - Green(RX

4 Communication settings and guide of HMI connecting with controller 4. Click “online/login” ◎Supported Device Device Bit Address Word Address For

Página 337 - S2PU72A:

4 Communication settings and guide of HMI connecting with controller NOTE: Baud Rate and Station No. must be the same as the setting in the controlle

Página 338

4 Communication settings and guide of HMI connecting with controller b. If the "No", the main station or other equipment necessary to config

Página 339 - - 336

2 Printer connectiong cable diagram 2 Printer Connecting Cable Diagram 2.1 Serial Interface Printer Cable 2.1.1 Brightek thermal printer Users choose

Página 340 - TRIO protocol

4 Communication settings and guide of HMI connecting with controller 2. Copy “MT5020.EDS” to “C:\Program Files\Common Files\CAA -Targets\ StepServo\

Página 341 - RS485-4 communication

4 Communication settings and guide of HMI connecting with controller d. choose “CanMaster” right click “Append HMI-MT5020” e. Node ID: set slave sta

Página 342

4 Communication settings and guide of HMI connecting with controller g. PDO read and write setting h. define Global Variable - 59 -

Página 343

4 Communication settings and guide of HMI connecting with controller i. SDO setting,this step need program j. load the configuration into the PLC ◎

Página 344 - 8 pin Mini Din (male)

4 Communication settings and guide of HMI connecting with controller Device Bit Address Word Address Format Notes ———— LW8000~LW8999 DDDD NO

Página 345

4 Communication settings and guide of HMI connecting with controller RS485 ◎ Supported Device Device Bit Address Word Address Format Notes Inp

Página 346

4 Communication settings and guide of HMI connecting with controller Special Relay F 0-2047 ------ DDDD Z Register ------ Z 0-1029 DDDD Timer ---

Página 347

4 Communication settings and guide of HMI connecting with controller Series CPU Link Module COMM Type Parameter Cable Danfoss FC-300 RS485 on t

Página 348

4 Communication settings and guide of HMI connecting with controller 8-32 FC Port Baud Rate [0] 2400 Baud [1] 4800 Baud *[2] 9600 Baud 8-33 FC P

Página 349 - 4.79 Vigor Corporation

4 Communication settings and guide of HMI connecting with controller 4. R/W of process word: 1) Address of EPD register is 8000, is for saving input

Página 350

2 Printer connectiong cable diagram 15 RXD19 GND3 TXD5 GNDBright Printer 20 pin port Note:the red line is the first pinHMI9 pin serial port e. WH-E173

Página 351 - 4.80 XiLin Inverter

4 Communication settings and guide of HMI connecting with controller ◆Frequency of R W 0 m apping : If input 2000 to R W 0, frequency is 25H Z, and in

Página 352 - 4.81 Yamatake Corporation

4 Communication settings and guide of HMI connecting with controller loop 0 1 01 Preset reference value LSB 02 Preset reference value MSB 03 DC brak

Página 353

4 Communication settings and guide of HMI connecting with controller frequency is 25Hz, and “1” in the 29th bit means 12.5Hz, and so on. In short, the

Página 354

4 Communication settings and guide of HMI connecting with controller DVP RS485-2 communication Note: RS485 communication, we should change the value

Página 355 - - 352

4 Communication settings and guide of HMI connecting with controller 2. PLC connection with the Wpl207, monitoring changes in the value of D1120. for

Página 356

4 Communication settings and guide of HMI connecting with controller HMI terminal9pin D-SUB female\maleController RS485 terminal-+1 RX-6 RX+com0/com1

Página 357

4 Communication settings and guide of HMI connecting with controller Input Register (read only) ------ 3X1-65535 DDDDD Output Register ------ 4

Página 358

4 Communication settings and guide of HMI connecting with controller 4708H PB Proportional band 1 to 9999, unit is 0.1. In the adjusting mode 4709

Página 359 - Yaskawa SGDM protocol

4 Communication settings and guide of HMI connecting with controller Address Content Explanation 1000H Process value (PV) Measuring unit is 0.1, u

Página 360 - - 357

4 Communication settings and guide of HMI connecting with controller used ) in the adjusting mode or 1012H Hysteresis setting value of the 1st ou

Página 361

2 Printer connectiong cable diagram 3 RXD7 GND3 TXD5 GNDHMI9 pin serial portPrinter25 pin port 2.2 Recommend Optional printer Printer Driver Printe

Página 362

4 Communication settings and guide of HMI connecting with controller 1026H Upper-limit alarm 2 In the setting mode 1027H Lower-limit alarm 2 I

Página 363

4 Communication settings and guide of HMI connecting with controller mode 0812H Decimal point position selection Except for the thermocouple B, S

Página 364 - - 361

4 Communication settings and guide of HMI connecting with controller ETC RS485-2 on the CPU unit EUC RS485-2 on the CPU unit EPC RS485-2 on the CPU

Página 365

4 Communication settings and guide of HMI connecting with controller ◎Cable Diagram RS485 communication cable com0/com11RX-6RX+5 GNDHMI terminal9pin D

Página 366 - V series inverter

4 Communication settings and guide of HMI connecting with controller Emerson EC10 RS485-2 communication Emerson EC20 RS485-2 communication NOTE: Co

Página 367

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Emerson EC10 Device Bit Address Word Address Format Notes Inp

Página 368 - Yokogawa FA-M3

4 Communication settings and guide of HMI connecting with controller Emerson EC20 Device Bit Address Word Address Format Notes Input Relay X000-377

Página 369 - Ethernet(TCP Slave)

4 Communication settings and guide of HMI connecting with controller 4.20 Epower ◎Serial Communication Series CPU Link Module Driver Epower Epowe

Página 370

4 Communication settings and guide of HMI connecting with controller ◎Supported Device Device Bit Address Word Address Format Notes UPSSet UPSSet

Página 371 - - 368

4 Communication settings and guide of HMI connecting with controller PC terminal9pin D-SUB femaleHMI terminal9pin D-SUB male3 TXD2 RXD5 GND2 RXD3 TXD5

Página 372

3 Download cable diagram 3 Download Cable Diagram 3.1 Download by Serial Port The COM2 port on the back of the case can be used to connect PLC RS-232

Página 373

4 Communication settings and guide of HMI connecting with controller FACON FB FB MA FB MC FBs-20MAT RS232 on the CPU unit RS232 Setting Your owner c

Página 374 - 4.84 YuDian AI

4 Communication settings and guide of HMI connecting with controller Modbus RTU RS485-2 communication Note: The detailed communication configuration

Página 375

4 Communication settings and guide of HMI connecting with controller PLC Setting 1、 In ether cfg software, click [scan] to search the PLC information

Página 376 - - 373

4 Communication settings and guide of HMI connecting with controller 3、 Click [ok] to save the settings. ◎Supported Device Device Bit Address Word A

Página 377 - - 374

4 Communication settings and guide of HMI connecting with controller FBS-CB25-3 module communication RS232 communication cable Controller port1 termin

Página 378 - - 375

4 Communication settings and guide of HMI connecting with controller NOTE:When PLC is protected by password, protocol time out 2 is 65535, and the re

Página 379 - 4.85 ZiGuang Ethernet

4 Communication settings and guide of HMI connecting with controller Note:M_special address: 8000 in the PLC corresponds to 0 in the HMI. DW_special a

Página 380

4 Communication settings and guide of HMI connecting with controller IC693CPU351 IC693CPU352 IC693CPU360 IC693CPU363 IC693CPU364 IC693CPU374 IC693CSE3

Página 381

4 Communication settings and guide of HMI connecting with controller CPU340 CPU341 CPU350 CPU351 CPU352 CPU360 CPU363 CSE311 CSE313 CSE323 CSE331 CSE3

Página 382

4 Communication settings and guide of HMI connecting with controller RS485-4 Setting Your owner cable VersaMax Series CPU001/002/005 CPUE05 RS