Siemens IK PI · 2015
Industrial Wireless Communication
WirelessHART
SITRANS AW200 WirelessHART adapter
6
Design
SITRANS AW200 WirelessHART Adapter consists of
An enclosure with a fitted aerial
Electronics
A high-performance lithium battery unit
SITRANS AW200 Wireless-HART Adapter, assembly
The enclosure can be opened by loosening 4 screws. This
enables you to access the electronics and battery unit. The
battery unit is removed without the use of tools, since it is
connected to the housing with clips.
On the back of the enclosure is the connector with a fixing nut
onto which various different replaceable connecting pieces can
be screwed to mount the adapter straight onto a field device.
On the base of the enclosure is an optional cable inlet which can
be used for a cable gland. Up to 2 cables can be inserted for off-
set adapter installation.
Function
SITRANS AW200 WirelessHART Adapter. functional diagram
Measured values and diagnostic information of connected field
devices with HART communication are transmitted via a wired
connection to the WirelessHART adapter. The adapter transmits
this information in the form of wireless signals to the IE/WSN-PA
link, the Siemens WirelessHART gateway. From here, the infor-
mation is available to the network of the system.
If a field device with a 4 ... 20 mA output signal is connected to
the adapter, only the measured value will be transmitted.
Following configuration and integration into a WirelessHART net-
work, each WirelessHART adapter is able to recognize its neigh-
bors. It notes the strength of the wireless signal, synchronizes it-
self, receives network information and then establishes
connections to its neighbors in the wireless network. A Wire-
lessHART network organizes itself. Manual settings for organiza-
tion are not required.
Two and four-wire field devices can be connected to a Wire-
lessHART adapter. In the case of a connected two-wire field de-
vice, voltage can be supplied by the adapter. Where multiple
two-wire field devices are connected (multi drop operation), the
adapter must be connected to an external power supply.
The WirelessHART adapter may also be connected in parallel to
an already existing installation which consists of a power supply
and a HART field device.
1234
6
5
LED
Push button
Plug to connect battery
Battery compartment
Terminals 1 to 6
Terminal tag for HART modem
1
2
3
4
5
6
SIMATIC
system
SIMATIC ET 200
with HART support
ES OS MS
IE/WSN-
PA LINK
SITRANS
AW200
SITRANS
TF280
SITRANS
P280
DP/PA
LINK
Industrial Ethernet
PROFIBUS
Wireless
HART
PROFIBUS PA
Kap_06_IWC_en.book Seite 171 Dienstag, 7. Oktober 2014 1:47 13