Distributed Use of SIMATIC FS600 Laser Scanner in
Category 3 / SIL 2
Entry ID: 21330889
A&D Safety Integrated Page 32/51 AS-FE-I-010-V20-EN
Copyright © Siemens AG 2007 All rights reserved
21330889_as_fe_i_010_v20_en_lscanner.doc
Settings of the failsafe DI (F-DI)
The settings are displayed after double-clicking “4/8 F-DI DC24V”
(see “Overview picture”).
Screenshot Note
Parameters / F parameters:
DIP switch setting (9…0)
This value has to be set on the F module
(F-DI).
F-monitoring time (ms)
The F-monitoring time must be larger than
the call time of OB35.
Parameters / Module parameters:
Category 3 / PL d / SIL 2 is reached by
carrying out a cross-circuit detection. The
cyclic short-circuit test and the sensor
supply must be activated via the F module.
Short-circuit test
cyclic short-circuit test is activated (cross-
circuit detection).
Behavior after channel faults
The entire F module is passivated in the
event of a channel fault.
Parameters / Module parameters:
Assignment of channels:
Channel 0, 4
Channel 0 Position switch 1
channel 4: Position switch 2
The sensors define which zone pair must
be active.
Parameterization of the channels
Activated
Used channels are activated, unused
channels are deactivated.
Sensor supply
The internal sensor voltage is activated so
that the short-circuit test can be carried
out.
Evaluation of the sensors
Both position switches connected as single
channel.