Distributed Use of SIMATIC FS600 Laser Scanner in
Category 3 / SIL 2
Entry ID: 21330889
A&D Safety Integrated Page 30/51 AS-FE-I-010-V20-EN
Copyright © Siemens AG 2007 All rights reserved
21330889_as_fe_i_010_v20_en_lscanner.doc
Settings of the CPU 315F-2DP
The settings are displayed after double-clicking “CPU 315F-2 DP”
(see “Overview picture”).
Screenshot Note
OB35 is set to 50 ms (default value = 100 ms)
You must make sure that the F monitoring time is
greater than the call time of OB 35 (see "Settings of
the failsafe DI" or "Settings of the failsafe DO").
A password has to be created in order to be able to
set the parameter “CPU contains safety program”. It is
only in this case that all required F blocks for safe
operation of the F modules are generated during
compiling the hardware configuration of STEP 7.
Password used here: siemens
Set mode: "Test mode"
During Process Mode, the test functions such as
program status or monitor/modify variable are
restricted in such a way that the set permitted
increase in scan cycle time is not exceeded. Testing
with stop-points and gradual program execution
cannot be performed.
During Test Mode, all test functions can be used
without restrictions via PG/PC which can also cause
larger extensions of the cycle time.
Important: During test mode of the S7-CPU, you have
to make sure that the S7-CPU or the process can
“stand” large increases in cycle time.