8-10
Ladder Logic (LAD) for S7-300 and S7-400
C79000-G7076-C504-02
8.9 Reset Coil
The Reset Coil instruction is executed only if the RLO = 1. If the RLO = 1,
this instruction resets its specified address to 0. If the RLO = 0, the
instruction has no effect on its specified address. The address remains
unchanged.
The Reset Coil instruction is affected by the Master Control Relay (MCR).
For more information on how the MCR functions, see Section 20.5.
Table 8-8 Reset Coil Element and Parameter
LAD Element Parameter Data Type Memory Area Description
R
<address>
<address>
BOOL
TIMER
COUNTER
I, Q, M, T, C,
D, L
The address indicates the bit that is to
be reset.
Status Word Bits
BR CC 1 CC 0 OV OS OR STA RLO FC
Write 0 x 0
I 0.0
I 0.2
I 0.1 Q 4.0
R
The signal state of output Q 4.0 is reset to 0 if one
of the following conditions exists:
S The signal state is 1 at inputs I 0.0 and I 0.1
S Or the signal state is 0 at input I 0.2
If the RLO of the branch is 0, the signal state of
output Q 4.0 remains unchanged.
Figure 8-8 Reset Coil
Description
Bit Logic Instructions