Commissioning and optimization (software)
7.3 Commissioning and optimization of the drive application
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
93
JOG frequency
Parameter Description Setting
P1057 = 1 JOG Enable
P1057 = 0 JOG-function disabled
P1057 = 1 JOG-function enabled (default)
P1058 = 5 JOG frequency right
Frequency in Hz when the motor is being jogged in the clockwise direction.
P1059 = 5 JOG frequency left
Frequency in Hz when the motor is being jogged in the counter-clockwise direction.
P1060 = 45 JOG ramp-up time
Ramp-up time in seconds from 0 to the
maximum frequency (P1082). The JOG ramp-up
is limited by P1058 or P1059.
P1061 = 50 JOG ramp-down time
Ramp-down time in seconds from the maximum
frequency (P1082) to 0.
3
3
W
3 3
I
I
PD[
Additional setpoints
Parameters Description (parameter name and factory setting in bold) Setting
P1074 = 1.0 BI: Disable additional setpoint
P1075 = 775 CI: Additional setpoint
Specifies the source of the additional setpoint, which is added to the main setpoint.
P1076 = 1.0 CI: Additional setpoint scaling
Defines the source for scaling the additional setpoint.
General settings:
1: Scaling 1.0 (100%)
755: Analog input setpoint
1024: Fixed frequency setpoint
1050: MOP setpoint