Appendix
A.2 ESD directives
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
169
A.2.4.2 ET 200pro FC frequency converter in general industrial application
Explanatory notes for general industrial application
In this EMC application, the manufacturer/assembler must certify the devices used as
compliant with the EMC directive for industrial environments. The limit values are in line with
the generic standards EN 61000-6-4 for generic emissions (noise radiation) and EN 61000-
6-2 interference immunity in the second environment (industrial).
Limit values for general industrial application
The following tables contain the key limit values for compliance with the generic standards.
Table A-13 Limit values for noise radiation for general industrial application to EN 61000-6-4
EMC phenomena Basic standard for
test procedures
Limit value
Radiated emissions EN 55011 Class A, Group 1
Conducted emissions EN 55011 Class A, Group 1
Table A-14 Limit values for interference immunity for general industrial application to EN 61000-6-2
EMC phenomena Basic standard for
test procedures
Level Evaluation criterion
Voltage dips EN 61000-4-11 30% reduction, 0.5 periods B
Voltage interruptions EN 61000-4-11 > 95% reduction, 250 periods C
8 kV, air discharge B Electrostatic discharge EN 61000-4-2
4 kV, contact discharge B
2 kV electric power cable B Burst EN 61000-4-4
1 kV control cable B
2 kV electric power cable (phase
- ground)
B
1 kV electric power cable (phase
- phase)
B
Interference
pulses
Voltage surge EN 61000-4-5
1 kV control cable (cable -
ground)
B
High-frequency electromagnetic field,
amplitude-modulated
EN 61000-4-3 80 MHz – 1000 MHz, 10 V/m,
80 % AM
A
The requirements of the generic standards in respect of interference immunity are met. The
required values for interference emission are complied with if installation takes place