Series commissioning and operation
8.1 Transfer of the frequency converter parameter assignment
ET 200pro FC
126 Operating Instructions, 11/2007, A5E01100763B AA
8.1.3 Parameter transfer with MMC
Upload from frequency converter to an MMC
The frequency converter features an MMC slot, into which a memory card can be inserted.
An upload of parameters from EEPROM to the MMC can only be triggered manually.
Prerequisites:
● The upload frequency converter's power supply must be connected.
● The upload frequency converter must be in the "Ready" state.
● You must have an MMC, type 6SL3254-0AM00-0AA0, at your disposal.
Procedure
Parameters Description (Parameter name and default setting (if this does not vary) in bold) Setting
Disassemble frequency converter, insert MMC into rear of frequency converter and re-
assemble frequency converter - Carry out the following steps in respect of the parameter set
that is to be uploaded:
P0010 = 30 Commissioning parameter*
0: Ready
1: Quick comm.
2: Frequency converter
30: Factory setting, parameter transfer
95: Commissioning of fail-safe functions
P0804 = … Select clone file
0: clone00.bin
…
99: clone99.bin
Remark: You can use P0804 to select the name of the clone file. In theory, up to a maximum of
100 (0 ... 99) parameter sets can be stored on one MMC.
P0802 = 2 Transfer data from EEPROM
0: Disabled
2: Start MMC transfer
If the upload was successfully completed, P0010 and P0802 are set to 0 and the "RY/RDY"
LED is lit.
An unsuccessful upload is signaled by an error message.
Download from an MMC to the frequency converter
The transfer of parameters from the MMC to the frequency converter's EEPROM can be
triggered manually or performed automatically.