Siemens ET 757 E Series Instruções de Operação Página 37

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 190
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 36
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
37
Installation
4
4.1 Prerequisites and maximum expansion
Maximum mechanical expansion
The maximum expansion of an ET 200pro is reached when one of the rules outlined below
applies:
Table 4-1 Maximum mechanical expansion
Features Rule
Number of modules max. 16 electronic modules
Width of ET 200pro max. 1 m mounting width (without rack)
Number of frequency converters maximum 5
Maximum electrical expansion
Electronic / encoder supply 1L+:
Powers the internal electronics of the frequency converters
Electrically isolated to the backplane bus of ET 200pro, to 2L+ and to
PROFIBUS DP/PROFINET IO
Load voltage supply 2L+:
Powers the safe inputs and outputs when a safety-orientated frequency converter is
used
Electrically isolated to the backplane bus, to 1L+ and to PROFIBUS DP/
PROFINET IO
Table 4-2 Maximum electrical expansion
Features Rule
Electronic/encoder supply 1L+ max. 5 A per ET 200pro station; a frequency converter
requires 0.8 A
Load voltage supply 2L+ max. 10 A
per ET 200pro station
The load caused by the frequency converter is negligible
There is no electrical limit for a station that has been expanded with a maximum of 5
frequency converters.
Vista de página 36
1 2 ... 32 33 34 35 36 37 38 39 40 41 42 ... 189 190

Comentários a estes Manuais

Sem comentários