Commissioning and optimization (software)
7.4 Commissioning of communication between the S7 CPU and the frequency converter
ET 200pro FC
100 Operating Instructions, 11/2007, A5E01100763B AA
Status word 1 (ZSW1)
(Bits 0 to 10 according to PROFIdrive profile; bits 11 to 15 specifically for SINAMICS
frequency converters).
Table 7-9 Preassignment, status word 1
Bit Value Meaning Remarks
1 Ready to start Power supply switched on; electronics initialized;
pulses disabled.
0
0 Not ready to start --
1 Ready Frequency converter is switched on (ON command is
present); no fault enabled; frequency converter can run
as soon as the "Enable operation" command is issued.
See control word 1, bit 0
1
0 Not ready to start --
1 Operation enabled Drive follows setpoint. See control word 1, bit 3 2
0 Operation inhibited --
1 Fault present Drive is faulty. A fault is present in the drive; it is,
therefore, not operating and will switch back to the
"Begin start interlock" state once the fault has been
successfully eliminated and acknowledged.
3
0 No fault --
1 "Run down to
standstill" not enabled
-- 4
0 "Run down to
standstill" enabled
"Run down to standstill" (OFF2) command present.
1 "Rapid stop" not
enabled
-- 5
0 "Rapid stop" enabled "Rapid stop" (OFF3) command present.
1 Switch-on disabled The drive is then only transferred to the "Switched on"
state when the "Do not run down to standstill" AND "No
rapid stop" commands, followed by "ON", are issued.
6
0 Switch-on not
disabled
1 Warning present Drive still in operation; warning in service/maintenance
parameters; no acknowledgement; see interrupt
parameter r2110.
7
0 No warning No warning is present, or the warning has disappeared.
1 Speed deviation
within tolerance range
Setpoint/actual value deviation within tolerance range. 8
0 Speed deviation
outside of tolerance
range
--
1 Master control
requested
The automation system is requested to assume control.9
0 No control requested The master is not currently the master control.
10 1 Maximum frequency
reached or exceeded
Frequency converter output frequency is greater than
or equal to the maximum frequency.