Configuration / project engineering
5.3 Configuring the communication
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
59
5.3 Configuring the communication
The frequency converter is operated by means of PROFIdrive profile.
Table 5-1 Operation with standard telegram 1
Usable PLC Any PLC
Possible fieldbus PROFIBUS DP or PROFINET IO
Required blocks None
1
Communication between frequency converter and STARTER
commissioning software
Optional on the field bus
2 3
or across the RS232 port of the
frequency converter
Cyclic communication between higher-level PLC and frequency
converter
4 bytes
For details, refer to the "Standard telegram 1" table
Acyclic communication with a higher-level PLC DS 47 for transferring several parameters
2
Default diagnostics Channel-specific diagnostics (diagnostics number, slot number) with
OB82 called in higher-level SIMATIC CPU in the event of a
frequency converter fault
1 Optional: Drive ES block package
2 Only in PROFINET IO and PROFIBUS DPV1
3 Routing across one or several SIMATIC CPUs is not supported
Table 5-2 Standard telegram 1
SIMATIC PLC → frequency converter Frequency converter → SIMATIC PLC
Signal Remark Signal Remark
PZD1 STW1 Control word 1 ZSW1 Status word 1
PZD2 NSET_A Speed setpoint, 16
bit
NACT_A Speed actual value,
16 bit
5.3.1 Generating a hardware configuration for PROFIBUS in the SIMATIC Manager
Description
The following example of an ET 200pro FC frequency converter with an "IM 154-2 DP HF"
interface module will be used to demonstrate how to generate a PROFIBUS configuration
with HW Config in the SIMATIC Manager. This will take place in three steps:
Parameterizing the PROFIBUS DP interface in SIMATIC S7
Equipping the ET 200pro station
Settings for the frequency converter
Note
For information regarding the interface modules, please refer to the manual "ET 200pro
Distributed I/O System", chapter "Interface modules".
Parameterizing the PROFIBUS DP interface in SIMATIC S7
The PROFIBUS DP interface is parameterized when configuring the hardware. When a CPU
with integrated DP interface or a DP communication processor is selected from the hardware
Vista de página 58
1 2 ... 54 55 56 57 58 59 60 61 62 63 64 ... 189 190

Comentários a estes Manuais

Sem comentários