Siemens ET 757 E Series Instruções de Operação Página 35

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 190
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 34
Interfaces
3.2 PTC/KTY84 interface
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
35
3.1.3 MMC interface (Micro Memory Card)
Description
The MMC interface can be used to back up frequency converter parameters on an external
MMC and, if required, download them back onto the frequency converter.
Possible fields of application for the MMC
The MMC can be used as a parameter memory:
Uploading a parameter set onto an MMC
Transferring parameters from an MMC when exchanging the frequency converter
Automatic download of a parameter set from an MMC.
Note
Several parameter sets can be stored on an MMC. The file name clone00.bin is used in
the default setting. Other names can be set via P0804 (e.g., clone00.bin to clone99.bin).
Inserting the MMC
Precondition: The frequency converter must be disassembled.
The label must be facing down when the chamfered edge of the
MMC is pointing left.
The MMC must be pushed into the MMC slot as far as it will go;
it can only then be removed by pressing the eject button.
3.2 PTC/KTY84 interface
The PTC/KTY84 interface can be used as an option.
Description
The connection for a PTC/KTY84 sensor to the motor temperature monitor is integrated in
the motor connector.
WARNING
The motor temperature monitor is assigned to the line supply potential, dangerous touch
voltages are thus possible.
The frequency converter must be switched off-circuit before the motor temperature sensor
can be connected.