Commissioning and optimization (software)
7.4 Commissioning of communication between the S7 CPU and the frequency converter
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
105
Table 7-11 Parameter response
Word
Byte Byte
Request reference mirrored Request ID Response header
Drive object ID mirrored Qty Parameters
Format Qty Values
Values or error values
1. parameter value(s) (only after a
"request")
Format Qty Values
Values or error values
n. parameter value(s)
Description of the fields for a parameter request and response
Table 7-12 Description of the fields for parameter requests
Field Data type Values Remark
Unsigned 8 0x01 … 0xFF Request reference
Unambiguous identification of the request/response pair for the master. The
master changes the request reference with each new request. The slave mirrors
the request reference in its response.
Unsigned 8 0x01 0x02 Read request, write request Request ID
Specifies the request type. In the event of a write request the changes are saved
to volatile memory (RAM). A save operation is required in order to transfer the
data to non-volatile memory (P0971).
Unsigned 8 0x00 … 0xFF Number Drive object ID
Setting for the drive object number with a drive unit with more than one drive
object. Different drive objects with separate parameter number ranges can be
accessed at the same DPV1 connection.
Unsigned 8 0x01 … 0x27 No. 1 ... 39 Limited by the length of
the DPV1 telegram
Qty Parameters
In the case of multiple requests, defines the number of adjacent areas for the
parameter address and/or the parameter value for multiple parameter requests.
The number of parameters = 1 for individual requests.
Unsigned 8 0x10
0x20
0x30
Value Description Text (not
implemented)
Attribute
Type of parameter element being accessed.
Unsigned 8 0x00
0x01 … 0x75
Special function no. 1 ... 117 Limited
by the length of the DPV1 telegram
Qty of elements
Number of field elements being accessed.
Unsigned 16 0x0001 …
0xFFFF
No. 1 … 65535 Parameter number
Number of parameter being accessed.