Commissioning and optimization (software)
7.4 Commissioning of communication between the S7 CPU and the frequency converter
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
107
Table 7-13 Description of the fields for parameter requests
Field Data type Values Remark
Request positive,
status ok
Unsigned 8 0x01
0x02
0x81
0x82
Read request (+)
Write request (+)
Read request (–)
Write request (–)
Request negative,
error state
Request ID
Mirrors the request ID and indicates whether the execution of the request has
been positive or negative. Negative means: part of the - or the entire request
cannot be executed. The error values are transferred in place of the values for
every sub-response.
Drive object ID See the table above
Qty Parameters See the table above
Format See the table above
Qty Values See the table above
Values See the table above
Unsigned 16 0x0000 … 0x00FF Meaning of the error values: See
the next table
Error values
The error values in the event of a negative response. A zero byte is appended if
the values result in an odd number of bytes. This ensures integrity of the word
structure in the telegram.
Note
The DRIVE-ES SIMATIC block package provides function blocks within the standard block
libraries for writing/reading parameters, including a few examples.