UM344-2 ON-LINE AND OFF-LINE OPERATION
August 1995
2. Press and hold, for a minimum of 5 seconds, the
FULLSCALE pushbutton, then release the button.
Note the following.
• The "V", "%", and "PB" annunciators shall be lit
and the "PV" annunciator shall be extinguished.
• The displayed number is the VALVE position in
percent (-1 to 110).
• Interpreting a VALVE Open/Close position
depends upon knowing if the FINAL
CONTROL ELEMENT is configured as
REVERSE or DIRECT acting. For DIRECT
acting, 0% indicates a fully closed valve and
100% indicates a fully opened valve. The
opposite is true for a REVERSE acting
controller.
3. Select new VALVE between -1.0% and 110%.
Note the following.
• Cycling (pressing and releasing in less than 1
second) the ZERO or FULLSCALE pushbutton
respectively decrements or increments the
VALVE in 0.01 % increments.
• Pressing and holding either pushbutton, for more
than 1 second, initiates a special acceleration
mode whereby the VALVE changes in greater
and greater increments until limiting occurs.
• The new value is changed in RAM only and not
yet stored permanently in memory. If the
Pushbutton Mode times-out before storage is
accomplished, the Controller will operate with
the new VALVE; however, the new value will
be lost after a power-down or Master Reset.
E. Store New VALVE to Memory (new Power-Up Valve
in Auto Manual Transfer Block)
1. Simultaneously press and release both pushbuttons to
store new VALVE.
After VALVE storage, the Controller exits the