INSTALLATION UM344-2
September 1995
FIGURE 4-12 Signal (Loop) , Sensor, MXC and Test Terminals
4. Connect the loop cable to the SIGNAL (+) and (-) terminals inside the Transmitter's enclosure. Refer
to Figure 4-1, 4-2 or 4-3 for the needed connections for the type of Network. Terminals will
accommodate wire sizes up to 16 AWG. Attached to both signal terminals are lugs that facilitate the
connection of the MXC Communicator. DO NOT connect signal wires to the lugs.
IMPORTANT
The cable shield must be insulated from all terminals and the transmitter
enclosure. Refer to Section 4.3.11 for additional shielding and grounding
information.
5. Connect Sensor Wires
Hook each stripped solid wire end or insert each crimp-on terminal under the appropriate terminal
screw and tighten the screw for a reliable electrical connection. Refer to figures showing the needed
connections as listed below in paragraphs 1) to 4).
1) RTD Sensor - Connect the tagged RTD leads as shown in Figure 4-13 detail A, B, or C,
depending upon type of RTD used.
2) Thermocouple Sensor - Connect the tagged thermocouple extension leads as shown in Figure 4-13
detail D. The positive and negative thermocouple leads are usually color coded.
TESTSIGNAL
+ -
Ground
Screw
Signal (+)
Terminal
Signal (-)
Terminal
Test (+)
Terminal
Test (-)
Terminal
Notes:
1. Viewed with enclosure cap
removed.
2. MXC = Moore XTC
Communicator.
MXC
Connections
Thermocouple, RTD,
Ohms,or mV Input
Sensor Terminals for