INSTALLATION UM344-2
September 1995
4
-
6
FIGURE 4-1 Point-To-Point Network (Analog Mode)
FIGURE 4-2 Model 352 SLDC and Model 344 Connections (Analog Mode)
250
See
Note 1
Model 352
Rear
Terminals
See Note 4
A4
B5
MXC
AG
A5
Hazardous
Location
Non-Hazardous
Location
Notes:
1. Network resistance equals the sum of the barrier resistances and
the current sense resistor. Minimum value 250 Ohms; maximum value 1100 Ohms.
2. Connect the M XC (a Secondary Master) to the loop only in the non-hazardous location.
The MXC is a non-polar device.
3. Interconnect all cable shields and ground only at the power source.
4. Model 352 Rear Terminal Assignments
A4 - Analog Input 1 (AI1+)
A5 - Analog Input Common (AIC)
B5 - Two-Wire Transmitter Power (+26 Vdc)
AG - Case (Safety) Ground
See Installation And Service Instruction SD352 or User's Manual UM352-1
5. For access to Model 344 terminals, remove enclosure end cap.
6. Maximum loop cable length calculated by formula in Section 4.3.5.
Supply and
Return Barriers
Shown Above
See Note 3
See
Note 2
See Note 5
See Note 6
+
_
+
_
Signal Test
X02867S1
Model 344
Terminals